Summary for Test 2020-02-20-24-1

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 214680
DEA: 030F2854
EFIS: 0319000205
DIST-CO-RTE-PM03-SAC-99-7.1/9.4
Award Date04/06/2020
Closeout Date10/30/2020
Work DescriptionConstruct the temporary bridge superstructures, adjacent paving and pave temporary alignment
Location DescriptionNot set
QA Service Level1 (Verified on 03/02/2020)

Sample Information

Sample Taken Date02/20/2020 Sample Unique Key24
Date that the sample was received by the laboratory/organization performing the testing02/21/2020 Sample typeQuality Control
A brief description of the sample6"x12" Cylinders The quantity of what the sample constitutes2
From where was the sample collectedSource First name of sampler or witnessed byFerdinand
Last name of sampler or witnessed byRosal Title of samplerQC Technician
Telephone number of sampler Laboratory sample identification1B 2-20-20
Linked DIME Sample ID The fabricator/manufacturer/facility nameCon-Fab California, LLC
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier Structure nameVoided Slabs
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberVER-80LV
The truck number from where the sample was collected4th The batch plant ticket number from where the sample was collected5036
Concrete batch plantBP3 The fabricator/manufacturer designation for the sampleUnknown
A detailed description of where the material sample was collectedBed 2, 4th Truck Where the material sample would have been placed if not sampledUnknown
From Lot No.Unknown Bag Lot No.Unknown

Test Details

DIME Sample ID: 2020-02-20-24
DIME Test ID: 2020-02-20-24-1
Testing Lab: Con-Fab California Corporation - Lathrop
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2020-04-14

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Ferdinand Rosal
Date of test: 02/21/2020
Capped in accordance with?: ASTM C1231
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.00 in
Maximum load on cylinder 1: 126479 lb
Maximum load on cylinder 2: 124472 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Age of specimen: 1 days
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength (to nearest 10 psi): 4470 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 4/14/2020 ✔