Summary for Test 2026-04-28-79-5

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 994654
DEA: 07313504
EFIS: 0715000090
DIST-CO-RTE-PM07-LA,VEN-1-37.7/62.9,0.0/0.9
Award Date07/20/2023
Closeout DateNot set
Work DescriptionREMOVE AND CONSTRUCT BRIDGE AND CULVERTS.
Location DescriptionLOS ANGELES AND VENTURA COUNTIES AT VARIOUS LOCATIONS FROM 0.4 MILE SOUTH OF TEMESCAL CANYON ROAD TO 0.1 MILE NORTH OF TONGA STREET
QA Service Level1 (Verified on 07/24/2023)

Sample Information

Sample Taken Date04/28/2026 Sample Unique Key79
Date that the sample was received by the laboratory/organization performing the testing04/29/2026 Sample typeQuality Control
A brief description of the sample6x12 Cylinders The quantity of what the sample constitutes6
From where was the sample collectedJob Site First name of sampler or witnessed byErik
Last name of sampler or witnessed byVillalba Title of samplerField Technician
Telephone number of sampler Laboratory sample identificationORSLBD50 Set 2
Linked DIME Sample ID The fabricator/manufacturer/facility nameAssociated Ready Mix
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier Structure nameBridge Paving
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberORSLBD50
The truck number from where the sample was collected452 The batch plant ticket number from where the sample was collected6144117
Concrete batch plant The fabricator/manufacturer designation for the sampleSet 2
A detailed description of where the material sample was collectedE/B PCH Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2026-04-28-79
DIME Test ID: 2026-04-28-79-5
Testing Lab: G3 Quality, Incorporated - Cerritos
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2026-09-23

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Jose Garibaldo
Date of test: 05/26/2026
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 6.01 in
Average diameter of cylinder 2: 6.01 in
Average diameter of cylinder 3: 6.01 in
Maximum load on cylinder 1: 239633 lb
Maximum load on cylinder 2: 243325 lb
Maximum load on cylinder 3: 245447 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Type of fracture pattern of cylinder 3: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 28.37 in^2
Cross sectional area of cylinder 2: 28.37 in^2
Cross sectional area of cylinder 3: 28.37 in^2
Compressive strength (to nearest 10 psi): 8560 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 9/23/2026 ✔