Summary for Test 2025-02-26-1-1
Test performed: CTM 670-December 2013Project Information
| Project Identifiers | Project ID: 1000004 DEA: 033H5604 EFIS: 0318000014 |
|---|---|
| DIST-CO-RTE-PM | 03-PLA,NEV-20,80-VAR |
| Award Date | 05/10/2024 |
| Closeout Date | Not set |
| Work Description | STRUCTURAL CONC, BAR REINFORCING STEEL, BRIDGE REMOVAL, HMA, AND JPCP. |
| Location Description | PLACER AND NEVADA COUNTIES NEAR CISCO GROVE ON ROUTE 80 FROM 0.4 MILE WEST OF LAKE VALLEY OVERCROSSING TO 0.9 MILE EAST OF YUBA PASS SEPARATION AND OVERHEAD AND ON ROUTE 20 AT YUBA PASS SEPARATION AND OVERHEAD |
| QA Service Level | 1 (Verified on 01/18/2024) |
Sample Information
| Sample Taken Date | 02/26/2025 | Sample Unique Key | 1 |
|---|---|---|---|
| Will the laboratory/organization for which you are a member perform testing on this material sample? | No | Date that the sample was received by the laboratory/organization performing the testing | 03/07/2025 |
| Sample type | Quality Assurance | A brief description of the sample | #7 6'-7"dia. welded hoop |
| The quantity of what the sample constitutes | 654 | From where was the sample collected | Fabricator |
| First name of sampler or witnessed by | Adrian | Last name of sampler or witnessed by | Sanchez |
| Title of sampler | Telephone number of sampler | 2137133499 | |
| Laboratory sample identification | Linked DIME Sample ID | ||
| The fabricator/manufacturer/facility name | CMC Rebar | Transportation Laboratory (TL) Number | |
| Inspector Lot Number from the Transportation Laboratory (TL) Form | L159-025-25 | Structure unique identifier | |
| Structure name | Bid Item | Not set |
Material Information
| Material Type | SMTL TM5 - Welded Hoops | Production or Authorization Testing | Production Testing |
|---|---|---|---|
| Service or Ultimate | Ultimate | Rebar Heat Number(s) | 9005424 9005425 |
| Hoop Manufacturer Lot Number(s) | 1-5 | Material Standard Code | ASTM A706 |
| Material Grade | 60 | Rebar Size | #7 |
| Diameter of Hoop | 6'-7" | Epoxy Coated | No |
| Epoxy Coating Color | NA | Rebar Manufacturer | CMC Rebar |
| Welding Company | CMC Rebar San Bernardino | Coating Standards | Uncoated |
| Weld Type | Flash Welded |
Test Details
DIME Sample ID: 2025-02-26-1
DIME Test ID: 2025-02-26-1-1
Testing Lab: CT HQ - Sacramento Structural Materials Testing Laboratory
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Test Release Date: 2025-03-12
Test Results
Number of Samples: 8
Input Type: Measured
Tester's full name: Steven Paine
Date of test: 03/12/2025
UTM: NA
Temperature: 0 f
| Num | Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By |
|---|---|---|---|---|---|---|---|---|
| 1 | 1 | 1 | 7 | 0.60 | 57680 | 96000 | ok necking | Kleinfelder |
| 2 | 2 | 1 | 7 | 0.60 | 55980 | 93500 | ok necking | Kleinfelder |
| 3 | 3 | 1 | 7 | 0.60 | 57220 | 95500 | ok necking | Kleinfelder |
| 4 | 4 | 1 | 7 | 0.60 | 57770 | 96500 | ok necking | Kleinfelder |
| 5 | 1 | 5 | 7 | 0.60 | 57470 | 96000 | ok necking | Kleinfelder |
| 6 | 2 | 5 | 7 | 0.60 | 58830 | 98000 | ok necking | Kleinfelder |
| 7 | 3 | 5 | 7 | 0.60 | 58910 | 98000 | ok necking | Kleinfelder |
| 8 | 4 | 5 | 7 | 0.60 | 57650 | 96000 | ok necking | Kleinfelder |
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 3/12/2025 ✔