Summary for Test 2024-12-03-18-2

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 1000649
DEA: 061H3404
EFIS: 0625000042
DIST-CO-RTE-PM06-TUL-99-23.49
Award Date09/10/2024
Closeout Date05/09/2025
Work DescriptionBRIDGE REPAIR FOR BR #46 0192
Location DescriptionTulare County along NB SR 99 at Avenue 184 OC, Bridge #46 0192.
QA Service Level1 (Verified on 09/26/2024)

Sample Information

Sample Taken Date12/03/2024 Sample Unique Key18
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing12/04/2024
Sample typeQuality Assurance A brief description of the sampleconcrete from the bridge deck
The quantity of what the sample constitutes9.6 From where was the sample collectedJob Site
First name of sampler or witnessed byPao Last name of sampler or witnessed byMoua
Title of sampler Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameCALPORTLAND Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number18041H
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected216515
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedwheelbarrow Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2024-12-03-18
DIME Test ID: 2024-12-03-18-2
Testing Lab: CT D06 - Millbrook Field Laboratory
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2024-12-17

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Gurjeet Litt
Date of test: 12/17/2024
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 71780 lb
Maximum load on cylinder 2: 66970 lb
Maximum load on cylinder 3: 67240 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Type of fracture pattern of cylinder 3: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 14 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 5710.4 psi
Compressive strength of cylinder 2: 5327.8 psi
Compressive strength of cylinder 3: 5349.2 psi
Compressive strength (to nearest 10 psi): 5460 psi
General comments (publicly viewable) (Max 1000 characters): Required strenght 5000 psi @ 28 days

Test was verified on 12/17/2024