Summary for Test 2024-06-13-60-1

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 995061
DEA: 081J9104
EFIS: 0818000135
DIST-CO-RTE-PM08-RIV,SBD-10,15,60,62,91,etc.-Var
Award Date10/11/2023
Closeout Date06/09/2025
Work DescriptionMODIFYING CMS SYSTEMS, SIGN FOUNDATION AND SIGN STRUCTURE.
Location DescriptionRIVERSIDE AND SAN BERNARDINO COUNTIES AT VARIOUS LOCATIONS
QA Service Level1 (Verified on 08/15/2023)

Sample Information

Sample Taken Date06/13/2024 Sample Unique Key60
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing06/14/2024
Sample typeQuality Assurance A brief description of the sample4x8
The quantity of what the sample constitutes11 From where was the sample collectedJob Site
First name of sampler or witnessed byNafisat Last name of sampler or witnessed byA
Title of samplerASR Telephone number of sampler
Laboratory sample identification1067-613 Linked DIME Sample ID
The fabricator/manufacturer/facility nameCemex Transportation Laboratory (TL) Number1067-613
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number1610974
The truck number from where the sample was collected10070472 The batch plant ticket number from where the sample was collected42859304
Concrete batch plantCEMEX FONTANA The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collected0.1 n/o Central Ave Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2024-06-13-60
DIME Test ID: 2024-06-13-60-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2024-07-17

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Matthew Clayton
Date of test: 06/20/2024
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.01 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 49140 lb
Maximum load on cylinder 2: 51600 lb
Maximum load on cylinder 3: 48130 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 1
Type of fracture pattern of cylinder 3: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 7 days
Cross sectional area of cylinder 1: 12.63 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 3890.7 psi
Compressive strength of cylinder 2: 4105.0 psi
Compressive strength of cylinder 3: 3829.0 psi
Compressive strength (to nearest 10 psi): 3940 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 7/17/2024