Summary for Test 2024-06-05-83-2
Test performed: CTM 524-March 2013Project Information
Project Identifiers | Project ID: 993870 DEA: 120R5604 EFIS: 1218000117 |
---|---|
DIST-CO-RTE-PM | 12-ORA-5,55,73,91,133,405-var |
Award Date | 04/12/2023 |
Closeout Date | Not set |
Work Description | PLACE RHMA-G, HMA, SLAB REPLACEMENT AND JPCP. |
Location Description | ORANGE COUNTY AT VARIOUS LOCATIONS |
QA Service Level | 1 (Verified on 06/14/2022) |
Sample Information
Sample Taken Date | 06/05/2024 | Sample Unique Key | 83 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 06/05/2024 |
Sample type | Quality Assurance | A brief description of the sample | RSC Flexural Beams |
The quantity of what the sample constitutes | 9 | From where was the sample collected | Job Site |
First name of sampler or witnessed by | G3 | Last name of sampler or witnessed by | G3 |
Title of sampler | Telephone number of sampler | ||
Laboratory sample identification | 24-0262 | Linked DIME Sample ID | |
The fabricator/manufacturer/facility name | G3 | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Concrete | The concrete mix design number | G3-23-PRS-346 |
---|---|---|---|
The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | 1 | |
Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
A detailed description of where the material sample was collected | Concrete from wheelbarrow | Where the material sample would have been placed if not sampled | Loc 5 NB 405 to SB 55 Connector |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2024-06-05-83
DIME Test ID: 2024-06-05-83-2
Testing Lab: CT D12 - Huntington Beach Field Laboratory
Test Method: CTM 524-March 2013: Method of Test for Flexural Strength Of Rapid Strength Concrete
Test Release Date: 2024-06-17
Test Results
Number of specimens: 3
Does the testing machine measure load or stress on the beam specimen?: Load
Fracture initiates in the tension surface: Within the Middle Third of the Span Length
Fracture occurred at a capped section: No
Is a beam dimensional correction factor used?: No
Input Type: Calculated
Tester's full name: Dan Morris
Date of test: 06/15/2024
Identification number: 4-6
Width of specimen: 6 inch
Width of specimen 2: 5.9375 inch
Width of specimen 3: 6.0625 inch
Depth of specimen: 6 inch
Depth of specimen 2: 6.0625 inch
Depth of specimen 3: 6.0625 inch
Span length of specimen: 18 inch
Span length of specimen 2: 18 inch
Span length of specimen 3: 18 inch
Maximum load applied: 6680 lb
Maximum load applied 2: 6410 lb
Maximum load applied 3: 6730 lb
Curing history and apparent moisture condition of the specimen: Sand pit/Lime water bath (Contract Specs.)
If specimen was capped, ground or if leather shims were used: No
Defects in specimen, including numbers of beams discarded during test: No
Age of specimen: 10 days
Age of specimen in hours: no data
Modulus of rupture: 580 psi
Modulus of rupture 2: 560 psi
Modulus of rupture 3: 570 psi
Modulus of rupture average: 570 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 6/17/2024 ✔