Summary for Test 2024-05-02-16-3

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 994820
DEA: 060V1104
EFIS: 0616000208
DIST-CO-RTE-PM06-FRE,KIN-5,41,198-Var
Award Date08/31/2023
Closeout DateNot set
Work DescriptionSTRATFORD KINGS RIVER BRIDGE REPLACEMENT.
Location DescriptionFRESNO AND KINGS COUNTIES AT VARIOUS LOCATIONS
QA Service Level1 (Verified on 09/20/2023)

Sample Information

Sample Taken Date05/02/2024 Sample Unique Key16
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing05/03/2024
Sample typeQuality Assurance A brief description of the sample4x8 concrete cylinders
The quantity of what the sample constitutes12- 4X8 Cylinders From where was the sample collectedJob Site
First name of sampler or witnessed byFares Last name of sampler or witnessed byThwabah
Title of samplerARE Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameMCM Construction Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier45-0110
Structure name

Material Information

Material TypeConcrete The concrete mix design number93T3G50
The truck number from where the sample was collected1 The batch plant ticket number from where the sample was collected158846
Concrete batch plantOutback The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedConcrete from wheelbarrow Where the material sample would have been placed if not sampledPier Caps 7&6
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2024-05-02-16
DIME Test ID: 2024-05-02-16-3
Testing Lab: CT D06 - Millbrook Field Laboratory
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2024-05-30

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Tomas Silva
Date of test: 05/30/2024
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.02 in
Average diameter of cylinder 2: 4.02 in
Average diameter of cylinder 3: 4.02 in
Maximum load on cylinder 1: 90540 lb
Maximum load on cylinder 2: 89850 lb
Maximum load on cylinder 3: 95200 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 5
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Correction factor for cylinder 3: 1
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.69 in^2
Cross sectional area of cylinder 2: 12.69 in^2
Cross sectional area of cylinder 3: 12.69 in^2
Compressive strength of cylinder 1: 7134.8 psi
Compressive strength of cylinder 2: 7080.4 psi
Compressive strength of cylinder 3: 7502 psi
Compressive strength (to nearest 10 psi): 7240 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 5/30/2024