Summary for Test 2022-03-01-18-3
Test performed: ASTM C109-16aProject Information
| Project Identifiers | Project ID: 8801 DEA: AML-CEM EFIS: AML-CEM |
|---|---|
| DIST-CO-RTE-PM | 59--- |
| Award Date | Not set |
| Closeout Date | Not set |
| Work Description | Special project for Cementitious Materials for use in Concrete Authorized Material List (AML) |
| Location Description | Not set |
| QA Service Level | NOT VERIFIED |
Sample Information
| Sample Taken Date | 03/01/2022 | Sample Unique Key | 18 |
|---|---|---|---|
| Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 03/01/2022 |
| Sample type | Authorization | A brief description of the sample | CCRL Blended cement |
| The quantity of what the sample constitutes | 1 Bucket | From where was the sample collected | Source |
| First name of sampler or witnessed by | na | Last name of sampler or witnessed by | na |
| Title of sampler | Telephone number of sampler | ||
| Laboratory sample identification | CM228090 | Linked DIME Sample ID | |
| The fabricator/manufacturer/facility name | CCRL Blended Cement | Transportation Laboratory (TL) Number | |
| Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
| Structure name | Bid Item | Not set |
Material Information
| Material Type | Cementitious | Brand | CCRL |
|---|---|---|---|
| Mill | Blended 90 | Type of Cementitious Material | Blended Cement |
Test Details
DIME Sample ID: 2022-03-01-18
DIME Test ID: 2022-03-01-18-3
Testing Lab: CT HQ - Sacramento Cement Testing Laboratory
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Test Release Date: 2022-04-14
Test Results
Will control cubes be used per ASTM C311?: no
Input Type: Measured
Tester's full name: Anthony Valdez
Date of test: 04/11/2022
Age of specimen: 7 days
The amount of flow : 109 %
The amount of water used : 47.8 %
Compressive strength of 1st specimen : 4422 psi
Compressive strength of 2nd specimen: 4629 psi
Compressive strength of 3rd specimen : 4593 psi
Average Compressive strength (to nearest 10 psi): 4550 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 4/14/2022 ✔