Sample Record

Owner Lab

  • CT D08 - Fontana Southern Regional Laboratory

DIME Sample ID 2019-02-01-6

Sample is locked from editing. info

Project Information

Project IdentifiersProject ID: 210569
DEA: 083555V4
EFIS: 0814000086
DIST-CO-RTE-PM08-SBD-15-42.5/46.0
Award Date11/05/2015
Closeout Date01/18/2022
Work DescriptionWIDEN I-15, RECONSTRUCT 3 IC'S, CONSTRUCT 2 NEW BR AND WIDEN 3 BR.
Location DescriptionSAN BERNARDINO COUNTY IN VICTORVILLE FROM 0.5 MILE NORTH OF MOJAVE DRIVE TO 1.5 MILE NORTH OF STODDARD WELLS ROAD OVERCROSSING
QA Service Level1 (Verified on 10/15/2015)

Sample Information

Sample Taken Date02/01/2019 Sample Unique Key6
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing02/08/2019
Sample typeQuality Assurance A brief description of the sample6x12 concrete cylinders
The quantity of what the sample constitutes2 From where was the sample collectedJob Site
First name of sampler or witnessed bymd Last name of sampler or witnessed byradman
Title of samplerTE Civil Telephone number of sampler
Laboratory sample identification934-201 Linked DIME Sample ID
The fabricator/manufacturer/facility nameagon inc ore grande Transportation Laboratory (TL) Number20190201
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifierMOJAVE RIVER BRIDGE WIDEN and NEW
Structure nameMOJAVE RIVER BRIDGE WIDEN and NEW

Material Information

Material TypeConcrete The concrete mix design numberSITI72A
The truck number from where the sample was collected181 The batch plant ticket number from where the sample was collected847114
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleAMES CONSTRUCTION
A detailed description of where the material sample was collected120 cy Where the material sample would have been placed if not sampledMOJAVE RIVER BRIDGE WIDEN and NEW
From Lot No.Unknown Bag Lot No.Unknown

Submitted Tests

DIME Test IDTest MethodTester Name, Testing LabDate TestedSubmitted ByVerified?Release DateTest CommentsActions
2019-02-01-6-1ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete SpecimensMM, CT D08 - Fontana Southern Regional Laboratory03/01/2019Minh Pham
Yes
03/08/2019

Sample File Attachments

File NameExtensionDate UploadedActions
No results found.

Test File Attachments


DIME Test ID: 2019-02-01-6-1 ASTM C39-10 (Verified)