Summary for Test 2020-07-15-25-1
Test performed: ASTM C39-10Project Information
Project Identifiers | Project ID: 214453 DEA: 07317504 EFIS: 0715000246 |
---|---|
DIST-CO-RTE-PM | 07-LA-5,101,405,and710-VariousLocations |
Award Date | 11/27/2019 |
Closeout Date | 01/20/2022 |
Work Description | REPLACE DRAINAGE PUMPING EQUIPMENT. |
Location Description | LOS ANGELES COUNTY AT VARIOUS LOCATIONS |
QA Service Level | 1 (Verified on 02/26/2020) |
Sample Information
Sample Taken Date | 07/15/2020 | Sample Unique Key | 25 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 07/20/2020 |
Sample type | Quality Assurance | A brief description of the sample | 6X12 |
The quantity of what the sample constitutes | 6 | From where was the sample collected | Job Site |
First name of sampler or witnessed by | ZAFAR | Last name of sampler or witnessed by | INAM |
Title of sampler | TE | Telephone number of sampler | |
Laboratory sample identification | 1014-81 | Linked DIME Sample ID | |
The fabricator/manufacturer/facility name | NP | Transportation Laboratory (TL) Number | 134681 |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Concrete | The concrete mix design number | 557237SLSP |
---|---|---|---|
The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | NP | |
Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
A detailed description of where the material sample was collected | CHUTE | Where the material sample would have been placed if not sampled | |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2020-07-15-25
DIME Test ID: 2020-07-15-25-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2020-07-22
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Jose Guzman
Date of test: 07/22/2020
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.02 in
Average diameter of cylinder 2: 6.02 in
Maximum load on cylinder 1: 74340 lb
Maximum load on cylinder 2: 73745 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 7 days
Cross sectional area of cylinder 1: 28.46 in^2
Cross sectional area of cylinder 2: 28.46 in^2
Compressive strength of cylinder 1: 2612.1 psi
Compressive strength of cylinder 2: 2591.2 psi
Compressive strength (to nearest 10 psi): 2600 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 7/22/2020 ✔