Summary for Test 2014-10-23-13-1

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 7566
DEA: 042640K4
EFIS: 0412000406
COOP: 0412458
DIST-CO-RTE-PM04---
Award Date11/02/2012
Closeout Date06/03/2020
Work DescriptionNot set
Location DescriptionNot set
QA Service Level1 (Verified on 06/03/2020)

Sample Information

Sample Taken Date10/23/2014 Sample Unique Key13
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing10/31/2014
Sample typeVerification A brief description of the sampleconcrete cylinders
The quantity of what the sample constitutes2 cylinders From where was the sample collectedOther
First name of sampler or witnessed byPaul Last name of sampler or witnessed byWells
Title of samplerInspector Telephone number of sampler5103856899
Laboratory sample identification203402 Linked DIME Sample ID0
The fabricator/manufacturer/facility nameShamrock Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifierUnknown
Structure nameUnknown

Material Information

Material TypeConcrete The concrete mix design number4100A
The truck number from where the sample was collectedUnknown The batch plant ticket number from where the sample was collectedNA
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleUnknown
A detailed description of where the material sample was collectedFrom the truck Where the material sample would have been placed if not sampledNot set
From Lot No.Not set Bag Lot No.Not set

Test Details

DIME Sample ID: 2014-10-23-13
DIME Test ID: 2014-10-23-13-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2014-11-20

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: SV
Date of test: 11/20/2014
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.01 in
Average diameter of cylinder 2: 6.00 in
Maximum load on cylinder 1: 150289 lb
Maximum load on cylinder 2: 137392 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 28 days
Cross sectional area of cylinder 1: 28.37 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength of cylinder 1: 5297.5 psi
Compressive strength of cylinder 2: 4860.0 psi
Compressive strength (to nearest 10 psi): 5080 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Partner Data Point File
Test graph for Cylinder Code 1 of 2

Source: Partner Data Point File
Test graph for Cylinder Code 2 of 2

Test was verified on 11/20/2014