Summary for Test 2014-10-22-1-4
Test performed: ASTM C39-10Project Information
Project Identifiers | Project ID: 209175 DEA: 030F2204 EFIS: 0300000072 |
---|---|
DIST-CO-RTE-PM | 03-ED-50-R30.7/R31.7 |
Award Date | 02/25/2014 |
Closeout Date | 07/30/2015 |
Work Description | REPLACE BRIDGE. |
Location Description | SLY PARK UNDERCROSSING |
QA Service Level | 1 (Verified on 11/01/2013) |
Sample Information
Sample Taken Date | 10/22/2014 | Sample Unique Key | 1 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | No | Date that the sample was received by the laboratory/organization performing the testing | Not set |
Sample type | Verification | A brief description of the sample | 6x12 concrete cylinders |
The quantity of what the sample constitutes | 6 concrete cylinders | From where was the sample collected | Other |
First name of sampler or witnessed by | Brandon | Last name of sampler or witnessed by | Miller |
Title of sampler | Structure Representative | Telephone number of sampler | (916) 505-6839 |
Laboratory sample identification | Unknown | Linked DIME Sample ID | 0 |
The fabricator/manufacturer/facility name | Jobsite | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | 25 0042 | |
Structure name | Sly Park Rd UC |
Material Information
Material Type | Concrete | The concrete mix design number | SF718AFST0 |
---|---|---|---|
The truck number from where the sample was collected | 18 | The batch plant ticket number from where the sample was collected | 1051698 |
Concrete batch plant | 1B | The fabricator/manufacturer designation for the sample | Unknown |
A detailed description of where the material sample was collected | Discharge from concrete truck into wheelbarrow | Where the material sample would have been placed if not sampled | Not set |
From Lot No. | Not set | Bag Lot No. | Not set |
Test Details
DIME Sample ID: 2014-10-22-1
DIME Test ID: 2014-10-22-1-4
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2014-10-24
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Mike Mullins
Date of test: 10/24/2014
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.00 in
Maximum load on cylinder 1: 62206 lb
Maximum load on cylinder 2: 59631 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 2 days
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength of cylinder 1: 2200.4 psi
Compressive strength of cylinder 2: 2109.3 psi
Compressive strength (to nearest 10 psi): 2150 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 10/24/2014 ✔