Summary for Test 2014-09-19-5-1
Test performed: ASTM C39-10Project Information
Project Identifiers | Project ID: 7463 DEA: 042640U4 EFIS: 0412000195 |
---|---|
DIST-CO-RTE-PM | 04-SON-101-0.9/3.6 |
Award Date | 11/02/2012 |
Closeout Date | 06/03/2020 |
Work Description | CONSTRUCT PETALUMA BLVD SOUTH INTERCHANGE, REPLACE PETALUMA RIVER BR |
Location Description | SONOMA COUNTY IN AND NEAR PETALUMA FROM GUNN DRIVE TO ROUTE 101/116 SEPARATION AND OVERHEAD |
QA Service Level | 1 (Verified on 09/11/2012) |
Sample Information
Sample Taken Date | 09/19/2014 | Sample Unique Key | 5 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 09/26/2014 |
Sample type | Verification | A brief description of the sample | concrete cylinders |
The quantity of what the sample constitutes | 2 concrete cylinders | From where was the sample collected | Other |
First name of sampler or witnessed by | P | Last name of sampler or witnessed by | WELLS |
Title of sampler | Unknown | Telephone number of sampler | Unknown |
Laboratory sample identification | 258380 | Linked DIME Sample ID | 0 |
The fabricator/manufacturer/facility name | NA | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | Unknown | |
Structure name | Unknown |
Material Information
Material Type | Concrete | The concrete mix design number | NA |
---|---|---|---|
The truck number from where the sample was collected | Unknown | The batch plant ticket number from where the sample was collected | NA |
Concrete batch plant | Unknown | The fabricator/manufacturer designation for the sample | Unknown |
A detailed description of where the material sample was collected | Truck | Where the material sample would have been placed if not sampled | Not set |
From Lot No. | Not set | Bag Lot No. | Not set |
Test Details
DIME Sample ID: 2014-09-19-5
DIME Test ID: 2014-09-19-5-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2014-10-17
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Mike Mullins
Date of test: 10/17/2014
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.01 in
Average diameter of cylinder 2: 6.02 in
Maximum load on cylinder 1: 156687 lb
Maximum load on cylinder 2: 157277 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 28 days
Cross sectional area of cylinder 1: 28.37 in^2
Cross sectional area of cylinder 2: 28.46 in^2
Compressive strength of cylinder 1: 5523.0 psi
Compressive strength of cylinder 2: 5526.2 psi
Compressive strength (to nearest 10 psi): 5520 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 10/17/2014 ✔