Summary for Test 2014-07-30-5304338-1
Test performed: ASTM C39-10Project Information
Project Identifiers | Project ID: 208679 DEA: 100S1104 EFIS: 1000000229 COOP: 10406 |
---|---|
DIST-CO-RTE-PM | 10-SJ-4,5-Var |
Award Date | 12/16/2013 |
Closeout Date | 01/03/2019 |
Work Description | SR-4 FREEWAY EXTENSION |
Location Description | IN SAN JOAQUIN COUNTY |
QA Service Level | 1 (Verified on 03/25/2013) |
Sample Information
Sample Taken Date | 07/30/2014 | Sample Unique Key | 5304338 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 08/27/2014 |
Sample type | Quality Control | A brief description of the sample | concrete cylinder |
The quantity of what the sample constitutes | 2 concrete cylinder | From where was the sample collected | Other |
First name of sampler or witnessed by | Ferdinand | Last name of sampler or witnessed by | Rpsal |
Title of sampler | Telephone number of sampler | ||
Laboratory sample identification | cl141030 | Linked DIME Sample ID | Not set |
The fabricator/manufacturer/facility name | Con Fab | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Concrete | The concrete mix design number | trial batch |
---|---|---|---|
The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | na | |
Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
A detailed description of where the material sample was collected | na | Where the material sample would have been placed if not sampled | Not set |
From Lot No. | Not set | Bag Lot No. | Not set |
Test Details
DIME Sample ID: 2014-07-30-5304338
DIME Test ID: 2014-07-30-5304338-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2014-08-29
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Bang
Date of test: 08/27/2014
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.00 in
Maximum load on cylinder 1: 295040 lb
Maximum load on cylinder 2: 297510 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 4
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 28 days
Cross sectional area of cylinder 1: no data
Cross sectional area of cylinder 2: no data
Compressive strength (to nearest 10 psi): 10480 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 8/29/2014 ✔