Summary for Test 2017-05-08-12-13

Test performed: ASTM A370-15

Project Information

Project IdentifiersProject ID: 8196
DEA: 59912684
DIST-CO-RTE-PM59---
Award DateNot set
Closeout DateNot set
Work Description
Location Description
QA Service LevelNOT VERIFIED

Sample Information

Sample Taken Date05/08/2017 Sample Unique Key12
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing05/15/2017
Sample typeAcceptance A brief description of the sampleF1554 Grade 55 HDG Anchor Bolts
The quantity of what the sample constitutes6 From where was the sample collectedDistributor
First name of sampler or witnessed byK Last name of sampler or witnessed byChurchill
Title of samplerUnknown Telephone number of samplerUnknown
Laboratory sample identificationUnknown Linked DIME Sample IDUnknown
The fabricator/manufacturer/facility nameCMC Steel Nucor Transportation Laboratory (TL) NumberC970923
Inspector Lot Number from the Transportation Laboratory (TL) FormL02-025-17 Structure unique identifierNot set
Structure nameNot set

Material Information

Material TypeSMTL TM3 - Fastener Assembly Rocap Number(s)
Heat Number(s)PL16105348, 3068112 Nut Mfg. Lot Number(s)
Washer Mfg. Lot Number(s) Bolt SpecificationF1554 G55 HDG
Bolt Length(s)42" Nut Specificationna
Washer Specificationna FinishHDG
Diameter/Size1.25", 1.75" Bolt Mfg. Lot Number
Rocap Test Requirement(s) Lubricant Requirements(s)

Test Details

DIME Sample ID: 2017-05-08-12
DIME Test ID: 2017-05-08-12-13
Testing Lab: CT HQ - Sacramento Structural Materials Testing Laboratory
Test Method: ASTM A370-15: Standard Test Methods and Definitions for Mechanical Testing of Steel Products (Tensile - Round Sample)
Test Release Date: 2017-05-29

Test Results


Number of Samples: 4
Input Type: Calculated
Tester's full name: Arnold
Date of test: 05/22/2017
UTM: 67KIP
Temperature: 71 F
NumSampleHeat NumberDiameter (in)Area (sqin)Stress at Offset (psi)Tensile Strength (psi)Elongation in 4 x d (%)Tested By
1PL161053480.49950.196622928397028.7Arnold
2PL161053480.4930.1909630148471029.1Arnold
330681120.49450.1921613718729028.7Arnold
430681120.49550.1928621108733027.8Arnold

General comments (publicly viewable) (Max 1000 characters):
Test Graph

Test was verified on 5/22/2017