Summary for Test 2023-11-28-1-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 994851
DEA: 034J5004
EFIS: 0323000177
DIST-CO-RTE-PM03-SAC-51-0.24/0.24
Award Date05/08/2023
Closeout DateNot set
Work DescriptionNot set
Location DescriptionNot set
QA Service Level1 (Verified on 05/31/2023)

Sample Information

Sample Taken Date11/28/2023 Sample Unique Key1
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing11/28/2023
Sample typeQuality Assurance A brief description of the sample4x8 concrete cylinders
The quantity of what the sample constitutes12 Cylinders From where was the sample collectedJob Site
First name of sampler or witnessed bySpencer Last name of sampler or witnessed byAdams
Title of samplerMREA Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility namePrecision Volumetric Truck Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure nameFort Sutter Viaduct

Material Information

Material TypeConcrete The concrete mix design numberUnknown
The truck number from where the sample was collected The batch plant ticket number from where the sample was collectedUnknown
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedChute Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2023-11-28-1
DIME Test ID: 2023-11-28-1-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2023-11-28

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Spencer Adams
Date of test: 11/28/2023
Capped in accordance with?: ASTM C39 - Ground End
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 50588 lb
Maximum load on cylinder 2: 57945 lb
Maximum load on cylinder 3: 39455 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Type of fracture pattern of cylinder 3: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Correction factor for cylinder 3: 1
Age of specimen: 0 days
Age of specimen in hours: 3 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 4024.5 psi
Compressive strength of cylinder 2: 4609.8 psi
Compressive strength of cylinder 3: 3138.8 psi
Compressive strength (to nearest 10 psi): 3920 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 11/28/2023