Summary for Test 2023-10-26-35-1

Test performed: ASTM C39-21

Project Information

Project IdentifiersProject ID: 994326
DEA: 051C3604
EFIS: 0512000134
DIST-CO-RTE-PM05-SB-217-0.9/1.4
Award Date01/31/2023
Closeout DateNot set
Work DescriptionREPLACE BRIDGE.
Location DescriptionSANTA BARBARA COUNTY NEAR GOLETA FROM 0.2 MILE EAST OF GOLETA SLOUGH BRIDGE TO 0.4 MILE EAST OF SAN JOSE CREEK BRIDGE
QA Service Level1 (Verified on 10/17/2022)

Sample Information

Sample Taken Date10/26/2023 Sample Unique Key35
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing10/27/2023
Sample typeQuality Assurance A brief description of the sample4x12 cylinders
The quantity of what the sample constitutes3 cylinders From where was the sample collectedSource
First name of sampler or witnessed bySherri Last name of sampler or witnessed byBrannon
Title of samplerQA Inspector Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameKie-Con, Antioch Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name

Material Information

Material TypeConcrete The concrete mix design numberK5070-4212
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected119951
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedat Kie-Con Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2023-10-26-35
DIME Test ID: 2023-10-26-35-1
Testing Lab: CT HQ - QASI Bay Area Field Office
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2023-11-22

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Ryan Parr
Date of test: 11/22/2023
Apparent mass of submerged cylinder 1: 8.8475 lb
Average diameter of cylinder 1: 4.01 in
Average diameter of cylinder 2: 4.01 in
Average diameter of cylinder 3: 4.01 in
Maximum load on cylinder 1: 89160 lb
Maximum load on cylinder 2: 89551 lb
Maximum load on cylinder 3: 88605 lb
Type of fracture pattern of cylinder 1: 6
Type of fracture pattern of cylinder 2: 6
Type of fracture pattern of cylinder 3: 6
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.62 in^2
Cross sectional area of cylinder 2: 12.62 in^2
Cross sectional area of cylinder 3: 12.62 in^2
Compressive strength (to nearest 10 psi): 7060 psi
Serial number of delivery ticket, if available: no data
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 11/22/2023