Summary for Test 2023-10-03-79-1

Test performed: CTM 523-May 2020

Project Information

Project IdentifiersProject ID: 215348
DEA: 060U4204
EFIS: 0616000004
DIST-CO-RTE-PM06-FRE-99-R4.9/11.6
Award Date02/25/2021
Closeout DateNot set
Work DescriptionCONSTRUCT CRCP, PLACE HMA, AND ROADWAY EXCAVATION.
Location DescriptionFRESNO COUNTY IN AND NEAR SELMA AND FOWLER FROM MCCALL AVENUE UNDERCROSSING TO 0.5 MILE NORTH OF MERCED STREET UNDERCROSSING
QA Service Level1 (Verified on 12/07/2020)

Sample Information

Sample Taken Date10/03/2023 Sample Unique Key79
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing10/05/2023
Sample typeDepartment Acceptance A brief description of the sampleAceptance
The quantity of what the sample constitutesPer 1000 CY From where was the sample collectedManufacturer
First name of sampler or witnessed byNoha Last name of sampler or witnessed byHunt
Title of samplerConsultant Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameSecurity Paving batch plant Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name

Material Information

Material TypeConcrete The concrete mix design numberG3-22-PCC-291
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected000
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedConcrete from wheelbarrow Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2023-10-03-79
DIME Test ID: 2023-10-03-79-1
Testing Lab: CT D06 - Millbrook Field Laboratory
Test Method: CTM 523-May 2020: Method of Test for Flexural Strength of Concrete
Test Release Date: 2023-11-01

Test Results


Number of specimens: 3
Unit system used?: US Units
Does the testing machine measure load or stress on the beam specimen?: Load
Fracture initiates in the tension surface: Within the Middle Third of the Span Length
Is a beam dimensional correction factor used?: No
Input Type: Measured
Tester's full name: Gurjeet Litt
Date of test: 10/31/2023
Identification number: set # 2
Width of specimen: 6.05 inch
Width of specimen 2: 6.05 inch
Width of specimen 3: 6.00 inch
Depth of specimen: 6.10 inch
Depth of specimen 2: 6.00 inch
Depth of specimen 3: 6.00 inch
Span length of specimen: 18 inch
Span length of specimen 2: 18 inch
Span length of specimen 3: 18 inch
Maximum load applied: 7600 lb
Maximum load applied 2: 7800 lb
Maximum load applied 3: 7600 lb
Curing history and apparent moisture condition of the specimen: Moist Condition
If specimen was capped, ground or if leather shims were used: Leather shims
Defects in specimen: None
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Modulus of rupture: 610 psi
Modulus of rupture 2: 645 psi
Modulus of rupture 3: 635 psi
Modulus of rupture average: 630 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 11/1/2023