Summary for Test 2023-01-25-11-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 993776
DEA: 040J3004
EFIS: 0413000433
DIST-CO-RTE-PM04-SON-1-26.7/27.1
Award Date07/08/2022
Closeout DateNot set
Work DescriptionCONSTRUCTING RETAINING WALL AND CONFINEMENT SYSTEM TO RESTORE SLIPOUT.
Location DescriptionSONOMA COUNTY NEAR JENNER FROM 0.3 MILE TO 0.7 MILE NORTH OF MEYERS GRADE ROAD
QA Service Level1 (Verified on 05/11/2022)

Sample Information

Sample Taken Date01/25/2023 Sample Unique Key11
Will the laboratory/organization for which you are a member perform testing on this material sample?No Date that the sample was received by the laboratory/organization performing the testing01/03/2023
Sample typeQuality Assurance A brief description of the samplePiles 187-205 odds
The quantity of what the sample constitutes43 cy From where was the sample collectedJob Site
First name of sampler or witnessed bySylva Last name of sampler or witnessed byNwankwo
Title of samplerASR Telephone number of sampler713-498-8137
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameCanyon Rock - Forestville Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier20-E0110
Structure nameSlidesville Retaining Wall

Material Information

Material TypeConcrete The concrete mix design number72203043F
The truck number from where the sample was collected The batch plant ticket number from where the sample was collectedTBD
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedCHUTE Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2023-01-25-11
DIME Test ID: 2023-01-25-11-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2023-02-02

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: SA
Date of test: 02/02/2023
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 3.99 in
Average diameter of cylinder 2: 3.99 in
Maximum load on cylinder 1: 56505 lbf
Maximum load on cylinder 2: 52194 lbf
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 8 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 12.5 in^2
Cross sectional area of cylinder 2: 12.5 in^2
Compressive strength of cylinder 1: 4519.0 psi
Compressive strength of cylinder 2: 4174.0 psi
Compressive strength (to nearest 10 psi): 4350 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Bluehill Data Point File
Test graph for Cylinder Code 1 of 2

Source: Bluehill Data Point File
Test graph for Cylinder Code 2 of 2

Test was verified on 2/2/2023