Summary for Test 2022-11-19-6-1

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 993162
DEA: 07319104
EFIS: 0716000017
DIST-CO-RTE-PM07-LA-91-R11.8
Award Date02/10/2022
Closeout Date01/11/2024
Work DescriptionADJUST VERTICAL CLEARANCE WITH ROADWAY EXCAVATION AND PLACE JPCP.
Location DescriptionLOS ANGELES COUNTY IN LONG BEACH AT NORTHBOUND ROUTE 710 TO EASTBOUND ROUTE 91 CONNECTOR
QA Service Level1 (Verified on 11/30/2021)

Sample Information

Sample Taken Date11/19/2022 Sample Unique Key6
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing11/20/2022
Sample typeQuality Assurance A brief description of the sampleConcrete Cylinders LCBRS
The quantity of what the sample constitutes10 Cubic Yards From where was the sample collectedJob Site
First name of sampler or witnessed byRuben Last name of sampler or witnessed byLopez
Title of sampler Telephone number of sampler
Laboratory sample identification22-3090 Linked DIME Sample ID
The fabricator/manufacturer/facility namen/a Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name

Material Information

Material TypeConcrete The concrete mix design numberCTS-30-RAM
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected0
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedWheelbarrow Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2022-11-19-6
DIME Test ID: 2022-11-19-6-1
Testing Lab: Alta Vista Solutions - Whittier
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2022-12-08

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Nathan Ogbasellasie
Date of test: 11/26/2022
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 5.96 in
Average diameter of cylinder 2: 5.96 in
Maximum load on cylinder 1: 82209 lb
Maximum load on cylinder 2: 87845 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 7 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 27.9 in^2
Cross sectional area of cylinder 2: 27.9 in^2
Compressive strength (to nearest 10 psi): 3050 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 12/8/2022