Summary for Test 2022-09-06-58-1

Test performed: CTM 523-May 2020

Project Information

Project IdentifiersProject ID: 214573
DEA: 073096U4
EFIS: 0719000091
DIST-CO-RTE-PM07-LA-210-R0.0/R9.7
Award Date04/03/2020
Closeout Date06/06/2024
Work DescriptionPLACE CONCRETE PAVEMENT, BARRIER, HMA, DRAINAGE, AND ELECTRICAL.
Location DescriptionLOS ANGELES COUNTY IN LOS ANGELES FROM INTERSTATE 5 TO WHEATLAND AVENUE UNDERCROSSING
QA Service Level1 (Verified on 06/05/2020)

Sample Information

Sample Taken Date09/06/2022 Sample Unique Key58
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing09/07/2022
Sample typeDepartment Acceptance A brief description of the sampleJPCP
The quantity of what the sample constitutes10 CY From where was the sample collectedSource
First name of sampler or witnessed byChad Last name of sampler or witnessed byChotibhongs
Title of samplerMREA Telephone number of sampler231-817-0387
Laboratory sample identification22-2353 Linked DIME Sample ID
The fabricator/manufacturer/facility nameFlatiron Plant - Paxton off-Ramp Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name

Material Information

Material TypeConcrete The concrete mix design numberJPCP-3215-06
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected16
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedLoader Bucket at Flatiron Batch Plant Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2022-09-06-58
DIME Test ID: 2022-09-06-58-1
Testing Lab: CT D07 - Materials Field Laboratory, Unit 1953
Test Method: CTM 523-May 2020: Method of Test for Flexural Strength of Concrete
Test Release Date: 2022-10-05

Test Results


Number of specimens: 2
Unit system used?: US Units
Does the testing machine measure load or stress on the beam specimen?: Load
Fracture initiates in the tension surface: Within the Middle Third of the Span Length
Is a beam dimensional correction factor used?: No
Input Type: Measured
Tester's full name: Chad Chotibhongs
Date of test: 10/04/2022
Identification number: 22-2353
Width of specimen: 6 inch
Width of specimen 2: 6 inch
Depth of specimen: 6 inch
Depth of specimen 2: 6.06 inch
Span length of specimen: 18 inch
Span length of specimen 2: 18 inch
Maximum load applied: 9450 lb
Maximum load applied 2: 9460 lb
Curing history and apparent moisture condition of the specimen: ok
If specimen was capped, ground or if leather shims were used: 0
Defects in specimen: 0
Age of specimen: 28 days
Age of specimen in hours: no data
Modulus of rupture: 790 psi
Modulus of rupture 2: 770 psi
Modulus of rupture average: 780 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 10/5/2022