Summary for Test 2022-05-01-11-1

Test performed: CTM 524-March 2013

Project Information

Project IdentifiersProject ID: 214573
DEA: 073096U4
EFIS: 0719000091
DIST-CO-RTE-PM07-LA-210-R0.0/R9.7
Award DateNot set
Closeout DateNot set
Work DescriptionPLACE CONCRETE PAVEMENT, BARRIER, HMA, DRAINAGE, AND ELECTRICAL.
Location DescriptionLOS ANGELES COUNTY IN LOS ANGELES FROM INTERSTATE 5 TO WHEATLAND AVENUE UNDERCROSSING
QA Service Level1 (Verified on 06/05/2020)

Sample Information

Sample Taken Date05/01/2022 Sample Unique Key11
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing05/01/2022
Sample typeAcceptance A brief description of the sampleRapid set concrete beams
The quantity of what the sample constitutes594+ yd3 From where was the sample collectedManufacturer
First name of sampler or witnessed byRosauro Last name of sampler or witnessed byNogoy
Title of samplerTEC Telephone number of sampler2137939321
Laboratory sample identification22-1005 Linked DIME Sample ID
The fabricator/manufacturer/facility nameFlatiron Batch Plant - EB210 Paxton Offramp Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name

Material Information

Material TypeConcrete The concrete mix design number3215-JPCPRSC-12
The truck number from where the sample was collected0 The batch plant ticket number from where the sample was collected66
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedLoader from Flatiron Batch Plant Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2022-05-01-11
DIME Test ID: 2022-05-01-11-1
Testing Lab: CT D07 - Materials Field Laboratory, Unit 1953
Test Method: CTM 524-March 2013: Method of Test for Flexural Strength Of Rapid Strength Concrete
Test Release Date: 2022-05-12

Test Results


Number of specimens: 3
Does the testing machine measure load or stress on the beam specimen?: Load
Fracture initiates in the tension surface: Within the Middle Third of the Span Length
Fracture occurred at a capped section: No
Is a beam dimensional correction factor used?: No
Input Type: Measured
Tester's full name: Rosauro Nogoy
Date of test: 05/11/2022
Identification number: 22-1005
Width of specimen: 6 inch
Width of specimen 2: 6 inch
Width of specimen 3: 6 inch
Depth of specimen: 6.0625 inch
Depth of specimen 2: 6.0625 inch
Depth of specimen 3: 6.0625 inch
Span length of specimen: 18 inch
Span length of specimen 2: 18 inch
Span length of specimen 3: 18 inch
Maximum load applied: 9108 lb
Maximum load applied 2: 9219 lb
Maximum load applied 3: 8876 lb
Curing history and apparent moisture condition of the specimen: 0
If specimen was capped, ground or if leather shims were used: 0
Defects in specimen, including numbers of beams discarded during test: 0
Age of specimen: 10 days
Age of specimen in hours: no data
Modulus of rupture: 780 psi
Modulus of rupture 2: 790 psi
Modulus of rupture 3: 760 psi
Modulus of rupture average: 780 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 5/12/2022