Summary for Test 2021-07-23-18-1
Test performed: ASTM C39-17aProject Information
Project Identifiers | Project ID: 212896 DEA: 04160304 EFIS: 0400000429 |
---|---|
DIST-CO-RTE-PM | 04-ALA-84-13.1/13.5 |
Award Date | 12/15/2020 |
Closeout Date | Not set |
Work Description | NILES CANYON ALAMEDA CREEK BRIDGE REPLACEMENT |
Location Description | IN FREMONT, AT ALAMEDA CREEK BRIDGE (BR 33-0036). |
QA Service Level | 1 (Verified on 09/16/2019) |
Sample Information
Sample Taken Date | 07/23/2021 | Sample Unique Key | 18 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 08/04/2021 |
Sample type | Quality Assurance | A brief description of the sample | 6x12 concrete cylinders |
The quantity of what the sample constitutes | 2 Cylinders | From where was the sample collected | Job Site |
First name of sampler or witnessed by | Shady | Last name of sampler or witnessed by | Besada |
Title of sampler | ASR | Telephone number of sampler | |
Laboratory sample identification | Linked DIME Sample ID | ||
The fabricator/manufacturer/facility name | Viking Construction Company | Transportation Laboratory (TL) Number | 197225 |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name | Pier 4 120 inch CIDH |
Material Information
Material Type | Concrete | The concrete mix design number | DDGPV2Q3 |
---|---|---|---|
The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | 3 | |
Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
A detailed description of where the material sample was collected | Concrete Truck | Where the material sample would have been placed if not sampled | |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2021-07-23-18
DIME Test ID: 2021-07-23-18-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2021-08-20
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: SA
Date of test: 08/20/2021
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.01 in
Average diameter of cylinder 2: 6.01 in
Maximum load on cylinder 1: 241350 lbf
Maximum load on cylinder 2: 254190 lbf
Type of fracture pattern of cylinder 1: 4
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Age of specimen: 28 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.37 in^2
Cross sectional area of cylinder 2: 28.37 in^2
Compressive strength of cylinder 1: 8,508.0 psi
Compressive strength of cylinder 2: 8,960.0 psi
Compressive strength (to nearest 10 psi): 8730 psi
General comments (publicly viewable) (Max 1000 characters):