Summary for Test 2021-04-06-32-1
Test performed: ASTM C39-17aProject Information
Project Identifiers | Project ID: 213746 DEA: 080Q75U4 EFIS: 0817000114 |
---|---|
DIST-CO-RTE-PM | 08-SBD,RIV-60-R4.6/R9.9, R0.0/12.2 |
Award Date | 04/18/2019 |
Closeout Date | 06/28/2022 |
Work Description | REPLACEMENT OF TWO OUTSIDE LANES AND CONCRETE SLABS |
Location Description | Not set |
QA Service Level | 1 (Verified on 06/17/2019) |
Sample Information
Sample Taken Date | 04/06/2021 | Sample Unique Key | 32 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 04/14/2021 |
Sample type | Quality Assurance | A brief description of the sample | concrete cylinders |
The quantity of what the sample constitutes | 6 | From where was the sample collected | Job Site |
First name of sampler or witnessed by | Sony | Last name of sampler or witnessed by | Pheng |
Title of sampler | Telephone number of sampler | ||
Laboratory sample identification | 999-406 | Linked DIME Sample ID | |
The fabricator/manufacturer/facility name | Short Load Concrete | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Concrete | The concrete mix design number | CTS-30-RAM |
---|---|---|---|
The truck number from where the sample was collected | NA | The batch plant ticket number from where the sample was collected | NA |
Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
A detailed description of where the material sample was collected | 60 WB Haven off ramp shoulder left turn lane south end station 1 50 | Where the material sample would have been placed if not sampled | |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2021-04-06-32
DIME Test ID: 2021-04-06-32-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2021-04-21
Test Results
Unit system used?: US Units
Number of specimens: 6
Test performed: With no density determined
Input Type: Measured
Tester's full name: Bahman Baghai
Date of test: 04/15/2021
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1: 6.02 in
Average diameter of cylinder 2: 6.02 in
Average diameter of cylinder 3: 6.02 in
Average diameter of cylinder 4: 6.02 in
Average diameter of cylinder 5: 6.02 in
Average diameter of cylinder 6: 6.02 in
Maximum load on cylinder 1: 27885 lb
Maximum load on cylinder 2: 27785 lb
Maximum load on cylinder 3: 27400 lb
Maximum load on cylinder 4: 28510 lb
Maximum load on cylinder 5: 27505 lb
Maximum load on cylinder 6: 27455 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Type of fracture pattern of cylinder 3: 1
Type of fracture pattern of cylinder 4: 1
Type of fracture pattern of cylinder 5: 1
Type of fracture pattern of cylinder 6: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Correction factor for cylinder 3: 1
Correction factor for cylinder 4: 1
Correction factor for cylinder 5: 1
Correction factor for cylinder 6: 1
Age of specimen: 9 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.46 in^2
Cross sectional area of cylinder 2: 28.46 in^2
Cross sectional area of cylinder 3: 28.46 in^2
Cross sectional area of cylinder 4: 28.46 in^2
Cross sectional area of cylinder 5: 28.46 in^2
Cross sectional area of cylinder 6: 28.46 in^2
Compressive strength of cylinder 1: 979.8 psi
Compressive strength of cylinder 2: 976.3 psi
Compressive strength of cylinder 3: 962.8 psi
Compressive strength of cylinder 4: 1001.8 psi
Compressive strength of cylinder 5: 966.4 psi
Compressive strength of cylinder 6: 964.7 psi
Compressive strength (to nearest 10 psi): 980 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 4/21/2021 ✔