Summary for Test 2021-01-09-3-2
Test performed: ASTM C39-17aProject Information
Project Identifiers | Project ID: 213746 DEA: 080Q75U4 EFIS: 0817000114 |
---|---|
DIST-CO-RTE-PM | 08-SBD,RIV-60-R4.6/R9.9, R0.0/12.2 |
Award Date | 04/18/2019 |
Closeout Date | 06/28/2022 |
Work Description | REPLACEMENT OF TWO OUTSIDE LANES AND CONCRETE SLABS |
Location Description | Not set |
QA Service Level | 1 (Verified on 06/17/2019) |
Sample Information
Sample Taken Date | 01/09/2021 | Sample Unique Key | 3 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 01/20/2021 |
Sample type | Quality Assurance | A brief description of the sample | CONCRETE CYLINDERS |
The quantity of what the sample constitutes | CONCRETE CYLINDERS | From where was the sample collected | Job Site |
First name of sampler or witnessed by | Paul | Last name of sampler or witnessed by | Pastora |
Title of sampler | RMA | Telephone number of sampler | |
Laboratory sample identification | 999-109A | Linked DIME Sample ID | |
The fabricator/manufacturer/facility name | Short Load Concrete Inc | Transportation Laboratory (TL) Number | 999-109A |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Concrete | The concrete mix design number | CTS-30-RAM |
---|---|---|---|
The truck number from where the sample was collected | NA | The batch plant ticket number from where the sample was collected | 8 |
Concrete batch plant | VOLUMETRIC TRUCK | The fabricator/manufacturer designation for the sample | |
A detailed description of where the material sample was collected | SITE | Where the material sample would have been placed if not sampled | sta 46000 60 fwy EB Haven Offramp |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2021-01-09-3
DIME Test ID: 2021-01-09-3-2
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2021-03-04
Test Results
Unit system used?: US Units
Number of specimens: 6
Test performed: With no density determined
Input Type: Measured
Tester's full name: Jose Guzman
Date of test: 01/20/2021
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 5.99 in
Average diameter of cylinder 2: 6.00 in
Average diameter of cylinder 3: 6.00 in
Average diameter of cylinder 4: 6.01 in
Average diameter of cylinder 5: 6.01 in
Average diameter of cylinder 6: 6.01 in
Maximum load on cylinder 1: 34600 lb
Maximum load on cylinder 2: 33970 lb
Maximum load on cylinder 3: 34820 lb
Maximum load on cylinder 4: 33990 lb
Maximum load on cylinder 5: 34360 lb
Maximum load on cylinder 6: 34380 lb
Type of fracture pattern of cylinder 1: 4
Type of fracture pattern of cylinder 2: 4
Type of fracture pattern of cylinder 3: 2
Type of fracture pattern of cylinder 4: 2
Type of fracture pattern of cylinder 5: 4
Type of fracture pattern of cylinder 6: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Correction factor for cylinder 3: 1
Correction factor for cylinder 4: 1
Correction factor for cylinder 5: 1
Correction factor for cylinder 6: 1
Age of specimen: 11 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.18 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Cross sectional area of cylinder 3: 28.27 in^2
Cross sectional area of cylinder 4: 28.37 in^2
Cross sectional area of cylinder 5: 28.37 in^2
Cross sectional area of cylinder 6: 28.37 in^2
Compressive strength of cylinder 1: 1227.8 psi
Compressive strength of cylinder 2: 1201.6 psi
Compressive strength of cylinder 3: 1231.7 psi
Compressive strength of cylinder 4: 1198.1 psi
Compressive strength of cylinder 5: 1211.1 psi
Compressive strength of cylinder 6: 1211.8 psi
Compressive strength (to nearest 10 psi): 1210 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 3/4/2021 ✔