Test 2017-04-10-9-3 (ASTM C39-17a) Summary

Project Information
Project IdentifiersProject ID: 209849
DEA: 07258404
EFIS: 0712000102
DIST-CO-RTE-PM07-LA-5-18.4/36.3
Work DescriptionIN LOS ANGELES COUNTY IN LOS ANGELES AND BURBANK AT VARIOUS LOCATION FROM ROUTE 60 TO ROUTE 170 CONSTRUCT GROSS SOLID REMOVAL DEVICES
Location DescriptionIN LOS ANGELES COUNTY, AT VARIOUS LOCATIONS FROM ROUTE 5/10SEPARATION TO 0.2 MILES NORTH OFFLECTCHER DRIVE UNDERCROSSING
Sample Information
Sample Taken Date4/10/2017 Sample Unique Key9
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing4/19/2017
Sample typeQuality Assurance A brief description of the sample12 x 6 concrete cylinder
The quantity of what the sample constitutes6 From where was the sample collectedJob Site
First name of sampler or witnessed byC Last name of sampler or witnessed byTong
Title of samplerASR Laboratory sample identification933-10
The fabricator/manufacturer/facility nameNATIONAL READY MIX Transportation Laboratory (TL) Number170410
Inspector Lot Number from the Transportation Laboratory (TL) FormUnknown Structure unique identifierUnknown
Structure nameUnknown
Material Information
Material TypeConcrete The concrete mix design numberS63061
The truck number from where the sample was collected472 The batch plant ticket number from where the sample was collected220194
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleUnknown
A detailed description of where the material sample was collectedCHUTE Where the material sample would have been placed if not sampledRW 9 AT AVSF FOOTING AT LOC 6
From Lot No.Unknown Bag Lot No.Unknown
Test Details
DIME Sample ID: 2017-04-10-9
DIME Test ID: 2017-04-10-9-3
Testing Lab: CT - Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2017-05-08
Test Results

Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Matthew Clayton
Date of test: 05/08/2017
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 5.98 in
Average diameter of cylinder 2: 5.97 in
Maximum load on cylinder 1: 123720 lb
Maximum load on cylinder 2: 125500 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 28 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.09 in^2
Cross sectional area of cylinder 2: 27.99 in^2
Compressive strength of cylinder 1: 4404.4 psi
Compressive strength of cylinder 2: 4483.7 psi
Compressive strength (to nearest 10 psi):4440 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 05/08/2017