Summary for Test 2022-09-13-12-4
Test performed: ASTM C39-21Project Information
Project Identifiers | Project ID: 993150 DEA: 051G9704 EFIS: 0516000008 |
---|---|
DIST-CO-RTE-PM | 05-SB-135-11.7/17.8 |
Award Date | 09/27/2021 |
Closeout Date | 03/28/2023 |
Work Description | COLD PLANE, OVERLAY ROADWAY WITH RHMA (GAP GRADED) AND ADA CURB RAMPS. |
Location Description | SANTA BARBARA COUNTY IN AND NEAR SANTA MARIA FROM LAKEVIEW ROAD TO NORTH SANTA MARIA CONNECTOR |
QA Service Level | 1 (Verified on 08/09/2021) |
Sample Information
Sample Taken Date | 09/13/2022 | Sample Unique Key | 12 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 09/13/2022 |
Sample type | Quality Assurance | A brief description of the sample | Class 2 Concrete |
The quantity of what the sample constitutes | 10 Cy | From where was the sample collected | Manufacturer |
First name of sampler or witnessed by | Isaac | Last name of sampler or witnessed by | Gleffe |
Title of sampler | ARET | Telephone number of sampler | 18053191237 |
Laboratory sample identification | 220913A | Linked DIME Sample ID | |
The fabricator/manufacturer/facility name | Calportland/Donaven | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Concrete | The concrete mix design number | 590GN1010 |
---|---|---|---|
The truck number from where the sample was collected | load 1 | The batch plant ticket number from where the sample was collected | load 1 |
Concrete batch plant | 590GN1010 | The fabricator/manufacturer designation for the sample | Class 2 concrete |
A detailed description of where the material sample was collected | On Job Site at Concrete Truck | Where the material sample would have been placed if not sampled | concrete barrier |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2022-09-13-12
DIME Test ID: 2022-09-13-12-4
Testing Lab: CT D05 - Santa Maria Field Laboratory
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2022-10-14
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Salvador Lopez-Zamora
Date of test: 10/11/2022
Capped in accordance with?: no data
Apparent mass of submerged cylinder 1: 0 lb
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.01 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 52029 lb
Maximum load on cylinder 2: 52029 lb
Maximum load on cylinder 3: 51588 lb
Type of fracture pattern of cylinder 1: 4
Type of fracture pattern of cylinder 2: 4
Type of fracture pattern of cylinder 3: 4
Comment on any defect in either specimen or caps (Max 250 Characters): NA
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: 112 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.6 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength (to nearest 10 psi): 4240 psi
Serial number of delivery ticket, if available: NA
General comments (publicly viewable) (Max 1000 characters): Complies
Test was verified on 10/14/2022 ✔