Summary for Test 2020-10-20-2-1
Test performed: ASTM C39-17aProject Information
Project Identifiers | Project ID: 212618 DEA: 044G0564 EFIS: 0417000154 |
---|---|
DIST-CO-RTE-PM | 04-ALA-680-M2.4/M12.4 |
Award Date | 11/16/2017 |
Closeout Date | 12/08/2022 |
Work Description | ROADWAY REHAB, BRIDGE REPLACEMENT, RET. WALLS, TOLL SYSTEMS |
Location Description | FREMONT AND AT SUNOL FROM MISSION BOULEVARD SEPARATION TO KOOPMAN ROAD UNDERCROSSING |
QA Service Level | 1 (Verified on 10/16/2017) |
Sample Information
Sample Taken Date | 10/20/2020 | Sample Unique Key | 2 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 10/21/2020 |
Sample type | Quality Assurance | A brief description of the sample | 6x12 concrete cylinders |
The quantity of what the sample constitutes | 2 cylinders | From where was the sample collected | Job Site |
First name of sampler or witnessed by | Jane | Last name of sampler or witnessed by | Lillard |
Title of sampler | Telephone number of sampler | ||
Laboratory sample identification | Linked DIME Sample ID | ||
The fabricator/manufacturer/facility name | Jobsite | Transportation Laboratory (TL) Number | 95707 |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Concrete | The concrete mix design number | 63 |
---|---|---|---|
The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | 00000000000000000 | |
Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
A detailed description of where the material sample was collected | Jobsite | Where the material sample would have been placed if not sampled | |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2020-10-20-2
DIME Test ID: 2020-10-20-2-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2020-10-27
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: PM
Date of test: 10/27/2020
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 5.98 in
Average diameter of cylinder 2: 5.97 in
Maximum load on cylinder 1: 203702 lbf
Maximum load on cylinder 2: 204868 lbf
Type of fracture pattern of cylinder 1: 4
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 7 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.09 in^2
Cross sectional area of cylinder 2: 27.99 in^2
Compressive strength of cylinder 1: 7253.0 psi
Compressive strength of cylinder 2: 7319.0 psi
Compressive strength (to nearest 10 psi): 7290 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Bluehill Data Point FileTest graph for Cylinder Code 1 of 2
Source: Bluehill Data Point File
Test graph for Cylinder Code 2 of 2
Test was verified on 10/27/2020 ✔