Summary for Test 2014-10-23-6-1
Test performed: ASTM C39-10Project Information
| Project Identifiers | Project ID: 7566 DEA: 042640K4 EFIS: 0412000406 COOP: 0412458 |
|---|---|
| DIST-CO-RTE-PM | 04--- |
| Award Date | 11/02/2012 |
| Closeout Date | 06/03/2020 |
| Work Description | Not set |
| Location Description | Not set |
| QA Service Level | 1 (Verified on 06/03/2020) |
Sample Information
| Sample Taken Date | 10/23/2014 | Sample Unique Key | 6 |
|---|---|---|---|
| Date that the sample was received by the laboratory/organization performing the testing | 10/31/2014 | Sample type | Verification |
| A brief description of the sample | concrete cylinders | The quantity of what the sample constitutes | 2 cylinders |
| From where was the sample collected | Other | First name of sampler or witnessed by | Paul |
| Last name of sampler or witnessed by | Wells | Title of sampler | Inspector |
| Telephone number of sampler | 5103856899 | Laboratory sample identification | 203403 |
| Linked DIME Sample ID | 0 | The fabricator/manufacturer/facility name | Shamrock |
| Transportation Laboratory (TL) Number | Inspector Lot Number from the Transportation Laboratory (TL) Form | ||
| Structure unique identifier | Unknown | Structure name | Unknown |
| Bid Item | Not set |
Material Information
| Material Type | Concrete | The concrete mix design number | 4100A |
|---|---|---|---|
| The truck number from where the sample was collected | Unknown | The batch plant ticket number from where the sample was collected | NA |
| Concrete batch plant | Unknown | The fabricator/manufacturer designation for the sample | Unknown |
| A detailed description of where the material sample was collected | From the truck | Where the material sample would have been placed if not sampled | Not set |
| From Lot No. | Not set | Bag Lot No. | Not set |
Test Details
DIME Sample ID: 2014-10-23-6
DIME Test ID: 2014-10-23-6-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2014-11-13
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: SV
Date of test: 11/13/2014
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.02 in
Average diameter of cylinder 2: 6.02 in
Maximum load on cylinder 1: 159386 lb
Maximum load on cylinder 2: 149636 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: no data
Age of specimen: 21 days
Cross sectional area of cylinder 1: 28.46 in^2
Cross sectional area of cylinder 2: 28.46 in^2
Compressive strength of cylinder 1: 5600.4 psi
Compressive strength of cylinder 2: 5257.8 psi
Compressive strength (to nearest 10 psi): 5430 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Partner Data Point FileTest graph for Cylinder Code 1 of 2
Source: Partner Data Point File
Test graph for Cylinder Code 2 of 2
Test was verified on 11/13/2014 ✔