Summary for Test 2019-09-18-4-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 213764
DEA: 080F0304
EFIS: 0800020358
DIST-CO-RTE-PM08-SBD-60-R0.7/R3.0
Award Date03/07/2019
Closeout Date07/27/2023
Work DescriptionREMOVE AND REPLACE THREE OVERCROSSING BRIDGES ON ROUTE 60
Location DescriptionIN SAN BERNARDINO COUNTY IN AND NEAR CHINO AT VARIOUS LOCATIONS FROM O.1 MILE WEST OF PIPELINE AVENUE OVERCROSSING TO 0.1 MILE EAST OF BENSON AVENUE OVERCROSSING
QA Service Level1 (Verified on 05/01/2019)

Sample Information

Sample Taken Date09/18/2019 Sample Unique Key4
Date that the sample was received by the laboratory/organization performing the testing09/18/2019 Sample typeControl Sample
A brief description of the sample4x8 Cylinders The quantity of what the sample constitutes3
From where was the sample collectedFabricator First name of sampler or witnessed byRigo
Last name of sampler or witnessed byMarin Title of samplerQAI
Telephone number of sampler951-500-0685 Laboratory sample identification1003-918B
Linked DIME Sample ID The fabricator/manufacturer/facility nameCon-Fab, Inc
Transportation Laboratory (TL) Number502 Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier Structure nameP5 3/3
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberSCC 9-8-25F
The truck number from where the sample was collectedUnknown The batch plant ticket number from where the sample was collected980
Concrete batch plantUnknown The fabricator/manufacturer designation for the samplebatch
A detailed description of where the material sample was collectedDischarge from concrete truck into wheelbarrow. Where the material sample would have been placed if not sampledUnknown
From Lot No.Unknown Bag Lot No.Unknown

Test Details

DIME Sample ID: 2019-09-18-4
DIME Test ID: 2019-09-18-4-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2019-10-18

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: MM
Date of test: 10/16/2019
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.01 in
Average diameter of cylinder 3: 4.01 in
Maximum load on cylinder 1: 132390 lb
Maximum load on cylinder 2: 132770 lb
Maximum load on cylinder 3: 131030 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Type of fracture pattern of cylinder 3: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.63 in^2
Cross sectional area of cylinder 3: 12.63 in^2
Compressive strength of cylinder 1: 10532.2 psi
Compressive strength of cylinder 2: 10512.3 psi
Compressive strength of cylinder 3: 10374.5 psi
Compressive strength (to nearest 10 psi): 10470 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 10/18/2019 ✔