Summary for Test 2018-08-25-1-1
Test performed: ASTM C39-17aProject Information
Project Identifiers | Project ID: 212731 DEA: 07318004 EFIS: 0715000280 |
---|---|
DIST-CO-RTE-PM | 07-LA-10-22.3/28.2 |
Award Date | 11/16/2017 |
Closeout Date | 06/16/2021 |
Work Description | TREAT BRIDGE DECK, CLOSURE POUR AND REPLACE JOINT SEALS. |
Location Description | LOS ANGELES COUNTY AT VARIOUS LOCATIONS FROM FREMONT AVENUE UNDERCROSSING TO RIO HONDO62 |
QA Service Level | 1 (Verified on 03/21/2018) |
Sample Information
Sample Taken Date | 08/25/2018 | Sample Unique Key | 1 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 08/28/2018 |
Sample type | Quality Assurance | A brief description of the sample | 6x12 concrete cylinders |
The quantity of what the sample constitutes | 4 | From where was the sample collected | Job Site |
First name of sampler or witnessed by | Thomas | Last name of sampler or witnessed by | Tong |
Title of sampler | ASR | Telephone number of sampler | Unknown |
Laboratory sample identification | 982-0825 | Linked DIME Sample ID | Unknown |
The fabricator/manufacturer/facility name | CTS SHORT LOAD RAPID SET | Transportation Laboratory (TL) Number | 20180825 |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Unknown | Structure unique identifier | 10 FWY WB RIO HONDO HOV LANE 1 APPROACH LABS |
Structure name | 10 FWY WB RIO HONDO HOV LANE 1 APPROACH LABS |
Material Information
Material Type | Concrete | The concrete mix design number | CTS-72-EHI |
---|---|---|---|
The truck number from where the sample was collected | 16 | The batch plant ticket number from where the sample was collected | na |
Concrete batch plant | Unknown | The fabricator/manufacturer designation for the sample | spectrum |
A detailed description of where the material sample was collected | LOAD 1 | Where the material sample would have been placed if not sampled | 10 FWY WB RIO HONDO HOV LANE 1 APPROACH LABS |
From Lot No. | Unknown | Bag Lot No. | Unknown |
Test Details
DIME Sample ID: 2018-08-25-1
DIME Test ID: 2018-08-25-1-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2018-09-07
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: MM
Date of test: 08/30/2018
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.01 in
Maximum load on cylinder 1: 197520 lb
Maximum load on cylinder 2: 191040 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 5 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.37 in^2
Compressive strength of cylinder 1: 6986.9 psi
Compressive strength of cylinder 2: 6733.9 psi
Compressive strength (to nearest 10 psi): 6860 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 8/31/2018 ✔