Summary for Test 2018-06-14-4-2
Test performed: ASTM C39-17aProject Information
Project Identifiers | Project ID: 209695 DEA: 08347704 EFIS: 0800000616 |
---|---|
DIST-CO-RTE-PM | 08-SBD-SR-58-0/12.9 |
Award Date | 11/10/2017 |
Closeout Date | 01/14/2021 |
Work Description | (Alternative Delivery) The CMGC project will upgrade SR 58 from 2- to 4-lanes in San Bernardino County from the Kern County line to 7.5 miles east of US-395. |
Location Description | SR-58 / 395 Kramer Junction project. In San Bernardino County from the Kern County line to 7.5 miles east of US-395. |
QA Service Level | 1 (Verified on 12/01/2017) |
Sample Information
Sample Taken Date | 06/14/2018 | Sample Unique Key | 4 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 06/18/2018 |
Sample type | Quality Assurance | A brief description of the sample | 6x12 concrete cylinders |
The quantity of what the sample constitutes | 4 | From where was the sample collected | Job Site |
First name of sampler or witnessed by | WASEAL | Last name of sampler or witnessed by | NAGI |
Title of sampler | ASR | Telephone number of sampler | Unknown |
Laboratory sample identification | 976-614 | Linked DIME Sample ID | Unknown |
The fabricator/manufacturer/facility name | ROBERTSON LUCERNE | Transportation Laboratory (TL) Number | 976-614 |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Unknown | Structure unique identifier | BENT CAP 6 AT BR NO 54 1325R |
Structure name | BENT CAP 6 AT BR NO 54 1325R |
Material Information
Material Type | Concrete | The concrete mix design number | SC799B38 |
---|---|---|---|
The truck number from where the sample was collected | 1695 | The batch plant ticket number from where the sample was collected | 3331782 |
Concrete batch plant | Unknown | The fabricator/manufacturer designation for the sample | KEWIT INFRASTRUCTURE |
A detailed description of where the material sample was collected | MIDLE | Where the material sample would have been placed if not sampled | BENT CAP 6 AT BR NO 54 1325R |
From Lot No. | Unknown | Bag Lot No. | Unknown |
Test Details
DIME Sample ID: 2018-06-14-4
DIME Test ID: 2018-06-14-4-2
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2018-07-20
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: IS
Date of test: 07/12/2018
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.01 in
Maximum load on cylinder 1: 129130 lb
Maximum load on cylinder 2: 135140 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 28 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.37 in^2
Compressive strength of cylinder 1: 4567.7 psi
Compressive strength of cylinder 2: 4763.5 psi
Compressive strength (to nearest 10 psi): 4670 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 7/13/2018 ✔