Summary for Test 2026-09-16-32-3
Test performed: CTM 521-June 2020Project Information
| Project Identifiers | Project ID: 1001723 DEA: 050N7064 EFIS: 0524000077 |
|---|---|
| DIST-CO-RTE-PM | 05-SB-101-10.9/12.3 |
| Award Date | Not set |
| Closeout Date | Not set |
| Work Description | SB 101 - Segment 4E North - Cabrillo |
| Location Description | Not set |
| QA Service Level | 1 (Verified on 11/03/2025) |
Sample Information
| Sample Taken Date | 09/16/2026 | Sample Unique Key | 32 |
|---|---|---|---|
| Date that the sample was received by the laboratory/organization performing the testing | 09/15/2026 | Sample type | Quality Assurance |
| A brief description of the sample | Concrete Test Samples | The quantity of what the sample constitutes | 90cy |
| From where was the sample collected | Supplier | First name of sampler or witnessed by | Eduardo |
| Last name of sampler or witnessed by | Gomez | Title of sampler | |
| Telephone number of sampler | Laboratory sample identification | ||
| Linked DIME Sample ID | The fabricator/manufacturer/facility name | CEMEX Santa Barbara | |
| Transportation Laboratory (TL) Number | Inspector Lot Number from the Transportation Laboratory (TL) Form | ||
| Structure unique identifier | Structure name | ||
| Bid Item | Not set |
Material Information
| Material Type | Concrete | The concrete mix design number | 1627310 |
|---|---|---|---|
| The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | 32142880 | |
| Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
| A detailed description of where the material sample was collected | Discharge from concrete truck into wheelbarrow. | Where the material sample would have been placed if not sampled | |
| From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2026-09-16-32
DIME Test ID: 2026-09-16-32-3
Testing Lab: CT D05 - Carpinteria Field Laboratory
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2026-10-14
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Michael Bennett
Date of test: 10/14/2026
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.02 in
Average diameter of cylinder 2: 4.02 in
Average diameter of cylinder 3: 4.02 in
Maximum load on cylinder 1: 115980 lb
Maximum load on cylinder 2: 115860 lb
Maximum load on cylinder 3: 117070 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 12.69 in^2
Cross sectional area of cylinder 2: 12.69 in^2
Cross sectional area of cylinder 3: 12.69 in^2
Compressive strength of cylinder 1: 9139.5 psi
Compressive strength of cylinder 2: 9130.0 psi
Compressive strength of cylinder 3: 9225.4 psi
Compressive strength (to nearest 10 psi): 9160 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 10/14/2026 ✔