Summary for Test 2026-09-19-28-3

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 1001169
DEA: 07314524
EFIS: 0722000300
COOP: 075283
DIST-CO-RTE-PM07---
Award Date07/03/2023
Closeout DateNot set
Work DescriptionI-105 METRO Express Lanes Project
Location DescriptionLA-105 PM R0.6/R10.1, LA-110 PM R14.1/R16.6
QA Service Level2 (Verified on 04/11/2025)

Sample Information

Sample Taken Date09/19/2026 Sample Unique Key28
Date that the sample was received by the laboratory/organization performing the testing08/19/2026 Sample typeQuality Assurance
A brief description of the sample6x12 concrete cylinders The quantity of what the sample constitutes120 CY
From where was the sample collectedJob Site First name of sampler or witnessed byCarlos
Last name of sampler or witnessed byViramontes Title of samplerMaterials Tester
Telephone number of sampler5628377377 Laboratory sample identification081926-ID905-105EBJPCP-1
Linked DIME Sample ID The fabricator/manufacturer/facility nameN/A
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier Structure name
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberCT632CPA
The truck number from where the sample was collectedTruck or Ticket 311866 The batch plant ticket number from where the sample was collectedLoad 12
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedJobsite Where the material sample would have been placed if not sampledJobsite
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2026-09-19-28
DIME Test ID: 2026-09-19-28-3
Testing Lab: Alta Vista Solutions - Whittier
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2026-10-06

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Carlos Viramontes
Date of test: 09/30/2026
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 5.97 in
Average diameter of cylinder 2: 5.97 in
Average diameter of cylinder 3: 5.97 in
Maximum load on cylinder 1: 151117 lb
Maximum load on cylinder 2: 149161 lb
Maximum load on cylinder 3: 152791 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 42 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 27.99 in^2
Cross sectional area of cylinder 2: 27.99 in^2
Cross sectional area of cylinder 3: 27.99 in^2
Compressive strength of cylinder 1: 5399.0 psi
Compressive strength of cylinder 2: 5329.1 psi
Compressive strength of cylinder 3: 5458.8 psi
Compressive strength (to nearest 10 psi): 5400 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 10/6/2026 ✔