Summary for Test 2026-08-17-75-1

Test performed: ASTM D638-Dec14

Project Information

Project IdentifiersProject ID: 1001246
DEA: 041Q7214
EFIS: 0423000277
DIST-CO-RTE-PM04-CC,CC,SOL-580,680,780-Var
Award Date09/25/2025
Closeout DateNot set
Work DescriptionINSTALL FIBER OPTIC CABLE SYSTEM, RAMP METERING, AND WIDEN ROADWAY.
Location DescriptionALAMEDA, CONTRA COSTA AND SOLANO COUNTIES AT VARIOUS LOCATIONS
QA Service Level1 (Verified on 08/13/2025)

Sample Information

Sample Taken Date08/17/2026 Sample Unique Key75
Date that the sample was received by the laboratory/organization performing the testing08/18/2026 Sample typeQuality Control
A brief description of the sample1 gallon can / HFST RESIN The quantity of what the sample constitutes2 Tankers
From where was the sample collectedSource First name of sampler or witnessed byGILBERTO
Last name of sampler or witnessed byGONZALEZ Title of samplerQuality Control Manager
Telephone number of sampler925-913-9199 Laboratory sample identification26-030
Linked DIME Sample ID The fabricator/manufacturer/facility nameKwik Bond Polymers, Benicia
Transportation Laboratory (TL) Number223KBP Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier Structure name
Bid ItemNot set

Material Information

Material TypeHigh Friction Surface Treatment Mgf. Lot Number(s)AZ6G01186
Batch NumberAZ6G01186 Mix NumberAZ6G01186
Resin Binder TypePolyester Used for OverlayYes
Used for InlayNo

Test Details

DIME Sample ID: 2026-08-17-75
DIME Test ID: 2026-08-17-75-1
Testing Lab: Future Labs, LLC
Test Method: ASTM D638-Dec14: Standard Test Method for Tensile Properties of Plastics
Test Release Date: 2026-10-02

Test Results


Number of specimens tested: 6
Input Type: Measured
Tester's full name: Alex Hamilton
Date of test: 10/01/2026
Conditioning procedure: 18/25/50+5/70
Speed of testing: 0.2 in/min
Sample 1 Width: 0.481 in
Sample 1 Thickness: 0.122 in
Sample 1 Area: 0.0587 in^2
Sample 1 Ultimate Strength Actual: 235 lbs
Sample 1 percent elongation: 49 %
Sample 1 Time: 0 MM:SS
Sample 2 Width: 0.483 in
Sample 2 Thickness: 0.125 in
Sample 2 Area: 0.0604 in^2
Sample 2 Ultimate Strength Actual: 245 lbs
Sample 2 percent elongation: 52 %
Sample 2 Time: 0 MM:SS
Sample 3 Width: 0.48 in
Sample 3 Thickness: 0.122 in
Sample 3 Area: 0.0586 in^2
Sample 3 Ultimate Strength Actual: 223 lbs
Sample 3 percent elongation: 43 %
Sample 3 Time: 0 MM:SS
Sample 4 Width: 0.48 in
Sample 4 Thickness: 0.131 in
Sample 4 Area: 0.0629 in^2
Sample 4 Ultimate Strength Actual: 232 lbs
Sample 4 percent elongation: 41 %
Sample 4 Time: 0 MM:SS
Sample 5 Width: 0.496 in
Sample 5 Thickness: 0.129 in
Sample 5 Area: 0.064 in^2
Sample 5 Ultimate Strength Actual: 241 lbs
Sample 5 percent elongation: 47 %
Sample 5 Time: 0 MM:SS
Sample 6 Width: 0.494 in
Sample 6 Thickness: 0.138 in
Sample 6 Area: 0.0682 in^2
Sample 6 Ultimate Strength Actual: 245 lbs
Sample 6 percent elongation: 45 %
Sample 6 Time: 0 MM:SS
Sample 1 Ultimate strength: 4003.4 psi
Sample 2 Ultimate strength : 4056.3 psi
Sample 3 Ultimate strength: 3805.5 psi
Sample 4 Ultimate strength: 3688.4 psi
Sample 5 Ultimate strength: 3765.6 psi
Sample 6 Ultimate strength : 3592.4 psi
Ultimate Strength Average: 3819 psi
Percent Elongation Average: 46 %
General comments (publicly viewable) (Max 1000 characters): Gel Time ASTM C881: 21 min. Cure Rate ASTM D1640: 90 min.

Test was verified on 10/2/2026 ✔