Summary for Test 2026-08-28-47-3

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 1001123
DEA: 051H4704
EFIS: 0516000078
DIST-CO-RTE-PM05-SCR-9-9-13.6,15.5
Award Date09/05/2025
Closeout DateNot set
Work DescriptionREPLACE BRIDGES AND INSTALL MGS.
Location DescriptionSANTA CRUZ COUNTY NEAR BOULDER CREEK AT SAN LORENZO RIVER BRIDGE AND AT KINGS CREEK BRIDGE
QA Service Level1 (Verified on 04/10/2025)

Sample Information

Sample Taken Date08/28/2026 Sample Unique Key47
Date that the sample was received by the laboratory/organization performing the testing08/28/2026 Sample typeQuality Control
A brief description of the sampleConcrete The quantity of what the sample constitutes100 cy
From where was the sample collectedJob Site First name of sampler or witnessed byArthur
Last name of sampler or witnessed bySchai Title of sampler
Telephone number of sampler Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameLas Animas Concrete
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier Structure name
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number779W30S-F
The truck number from where the sample was collected108 The batch plant ticket number from where the sample was collected404304
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedconcrete truck Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2026-08-28-47
DIME Test ID: 2026-08-28-47-3
Testing Lab: RMA Group - Rancho Cordova
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2026-09-30

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Todd Strait
Date of test: 09/25/2026
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 5.98 in
Maximum load on cylinder 1: 180916 lb
Maximum load on cylinder 2: 173006 lb
Type of fracture pattern of cylinder 1: 4
Type of fracture pattern of cylinder 2: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.09 in^2
Compressive strength (to nearest 10 psi): 6280 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 9/30/2026 ✔