Summary for Test 2026-08-11-51-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 994418
DEA: 040J5504
EFIS: 0414000012
DIST-CO-RTE-PM04-ALA-84-17.2/17.2
Award Date02/03/2026
Closeout DateNot set
Work DescriptionREPLACE BRIDGE, WIDEN ROADWAY, & CONSTRUCT SIDEWALKS.
Location DescriptionALAMEDA COUNTY AT SUNOL FROM SILVER SPRING ROAD UNDERPASS TO PLEASANTON SUNOL ROAD
QA Service Level1 (Verified on 12/01/2022)

Sample Information

Sample Taken Date08/11/2026 Sample Unique Key51
Date that the sample was received by the laboratory/organization performing the testing08/26/2026 Sample typeQuality Assurance
A brief description of the samplestructural concrete The quantity of what the sample constitutes27 CY
From where was the sample collectedJob Site First name of sampler or witnessed byMarcos
Last name of sampler or witnessed byLopez Title of samplerAssistant SR
Telephone number of sampler5104969610 Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameCemex
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier33-0774 Structure nameArroyo De La Laguna
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number1636582
The truck number from where the sample was collected76147 The batch plant ticket number from where the sample was collected4431A
Concrete batch plantCEMEX The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedBack of Truck Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2026-08-11-51
DIME Test ID: 2026-08-11-51-1
Testing Lab: CT HQ - Vallejo Field Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2026-09-08

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Nikhil Moon
Date of test: 09/08/2026
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 80380 lb
Maximum load on cylinder 2: 76670 lb
Maximum load on cylinder 3: 78625 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 6394.6 psi
Compressive strength of cylinder 2: 6099.4 psi
Compressive strength of cylinder 3: 6255.0 psi
Compressive strength (to nearest 10 psi): 6250 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 9/8/2026 ✔