Summary for Test 2018-03-06-5-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 211588
DEA: 030F3104
EFIS: 0300000078
DIST-CO-RTE-PM03-ED-49-23.6/24.5
Award Date12/12/2016
Closeout Date01/08/2019
Work DescriptionREPLACE BRIDGE.
Location DescriptionEL DORADO COUNTY NEAR COLOMA FROM 0.1 MILE EAST OF MARSHALL ROAD TO 0.3 MILE EAST OF LOTUS ROAD
QA Service Level1 (Verified on 10/19/2016)

Sample Information

Sample Taken Date03/06/2018 Sample Unique Key5
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing03/07/2018
Sample typeQuality Assurance A brief description of the sampleconcrete cylinders
The quantity of what the sample constitutes2 concrete cylinders From where was the sample collectedJob Site
First name of sampler or witnessed byM Last name of sampler or witnessed byMorgan
Title of samplerasr Telephone number of samplerUnknown
Laboratory sample identificationUnknown Linked DIME Sample IDUnknown
The fabricator/manufacturer/facility namefield Transportation Laboratory (TL) Number154478
Inspector Lot Number from the Transportation Laboratory (TL) FormUnknown Structure unique identifierUnknown
Structure nameUnknown

Material Information

Material TypeConcrete The concrete mix design numberna
The truck number from where the sample was collectedUnknown The batch plant ticket number from where the sample was collectedna
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleUnknown
A detailed description of where the material sample was collectedfield Where the material sample would have been placed if not sampledUnknown
From Lot No.Unknown Bag Lot No.Unknown

Test Details

DIME Sample ID: 2018-03-06-5
DIME Test ID: 2018-03-06-5-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2018-05-01

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Bang
Date of test: 05/01/2018
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.01 in
Average diameter of cylinder 2: 6.01 in
Maximum load on cylinder 1: 192074 lb
Maximum load on cylinder 2: 193795 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 56 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.37 in^2
Cross sectional area of cylinder 2: 28.37 in^2
Compressive strength of cylinder 1: 6770.3 psi
Compressive strength of cylinder 2: 6831.0 psi
Compressive strength (to nearest 10 psi): 6800 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Partner Data Point File
Test graph for Cylinder Code 1 of 2

Source: Partner Data Point File
Test graph for Cylinder Code 2 of 2

Test was verified on 5/1/2018