Summary for Test 2026-06-25-77-1

Test performed: ASTM C39-21

Project Information

Project IdentifiersProject ID: 1001123
DEA: 051H4704
EFIS: 0516000078
DIST-CO-RTE-PM05-SCR-9-9-13.6,15.5
Award Date09/05/2025
Closeout DateNot set
Work DescriptionREPLACE BRIDGES AND INSTALL MGS.
Location DescriptionSANTA CRUZ COUNTY NEAR BOULDER CREEK AT SAN LORENZO RIVER BRIDGE AND AT KINGS CREEK BRIDGE
QA Service Level1 (Verified on 04/10/2025)

Sample Information

Sample Taken Date06/25/2026 Sample Unique Key77
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing06/25/2026
Sample typeQuality Assurance A brief description of the sample4x8 Concrete Test Samples
The quantity of what the sample constitutes42 CY From where was the sample collectedFabricator
First name of sampler or witnessed byChris Last name of sampler or witnessed byLinan
Title of sampler Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameKie-Con Antioch Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name Bid ItemNot set

Material Information

Material TypePrecast Concrete The concrete mix design numberK25-087BG
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected127638
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedwheelbarrow Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2026-06-25-77
DIME Test ID: 2026-06-25-77-1
Testing Lab: CT HQ - Vallejo Field Laboratory
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2026-07-23

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Daniel Arreola
Date of test: 07/23/2026
Capped in accordance with?: ASTM C39 - Ground End
Apparent mass of submerged cylinder 1: 9 lb
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 106840 lb
Maximum load on cylinder 2: 105075 lb
Maximum load on cylinder 3: 88780 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 4
Type of fracture pattern of cylinder 3: 4
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 0 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 8500.0 psi
Compressive strength of cylinder 2: 8360.0 psi
Compressive strength of cylinder 3: 7060 psi
Compressive strength (to nearest 10 psi): 7970 psi
Serial number of delivery ticket, if available: no data
General comments (publicly viewable) (Max 1000 characters): All cylinder has pocket holes on the side and cylinder number 3 broke below strength

Test was verified on 7/23/2026