Summary for Test 2025-06-02-15-1

Test performed: ASTM C39-18

Project Information

Project IdentifiersProject ID: 1001249
DEA: 031N5504
EFIS: 0325000797
DIST-CO-RTE-PM03-BUT-70-35/36
Award Date02/03/2025
Closeout DateNot set
Work DescriptionMajor Damage Restoration
Location DescriptionBUT 70 Viaduct
QA Service Level1 (Verified on 05/06/2025)

Sample Information

Sample Taken Date06/02/2025 Sample Unique Key15
Date that the sample was received by the laboratory/organization performing the testing06/03/2025 Sample typeQuality Assurance
A brief description of the sampleBent 8 Right CIDH Pile Mix The quantity of what the sample constitutes9 CY
From where was the sample collectedJob Site First name of sampler or witnessed byJason
Last name of sampler or witnessed byCharmbury Title of samplerASR
Telephone number of sampler Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameMathews Ready Mix
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier12-0209 Structure nameConcow Sidehill Viaduct
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number072335F25O
The truck number from where the sample was collected842 The batch plant ticket number from where the sample was collected16033335
Concrete batch plantMathews Readymix Oroville The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedCHUTE FROM TRUCK Where the material sample would have been placed if not sampledBent 8 Right CIDH Pile
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2025-06-02-15
DIME Test ID: 2025-06-02-15-1
Testing Lab: CT D03 - Chico Field Laboratory
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2026-07-12

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Brad McKeehan
Date of test: 07/14/2025
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 103900 lb
Maximum load on cylinder 2: 106720 lb
Maximum load on cylinder 3: 104480 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 42 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 8265.7 psi
Compressive strength of cylinder 2: 8490.1 psi
Compressive strength of cylinder 3: 8311.9 psi
Compressive strength (to nearest 10 psi): 8360 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 7/12/2026 ✔