Summary for Test 2026-05-19-64-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 210094
DEA: 040G3604
EFIS: 0400000326
COOP: 042553A1,042981
DIST-CO-RTE-PM04-ALA-880,880-31.0/32.4
Award Date08/08/2025
Closeout DateNot set
Work DescriptionI-880 BROADWAY/ JACKSON INTERCHANGE: Modify Ramps, Hma Pvmt, Bridges, Drainage, Signals, Sw And Bikeway
Location DescriptionIN ALA COUNTY
QA Service Level1 (Verified on 10/17/2024)

Sample Information

Sample Taken Date05/19/2026 Sample Unique Key64
Will the laboratory/organization for which you are a member perform testing on this material sample?No Date that the sample was received by the laboratory/organization performing the testing05/28/2026
Sample typeQuality Assurance A brief description of the sampleStructural Concrete, Retaining Wall
The quantity of what the sample constitutes99 From where was the sample collectedJob Site
First name of sampler or witnessed byAbhiram Last name of sampler or witnessed byMallempati
Title of sampler Telephone number of sampler5107158789
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameCentral Concrete Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure nameRW105 Footing Bid Item3927478

Material Information

Material TypeConcrete The concrete mix design numberD20119EA
The truck number from where the sample was collected6320 The batch plant ticket number from where the sample was collected1076849
Concrete batch plantPleasanton The fabricator/manufacturer designation for the sampleCentral Concrete
A detailed description of where the material sample was collectedsample collected from concrete truck Where the material sample would have been placed if not sampledRW105 Footing
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2026-05-19-64
DIME Test ID: 2026-05-19-64-1
Testing Lab: CT HQ - Vallejo Field Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2026-06-16

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Mario Periera Vaz
Date of test: 06/16/2026
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 50945 lb
Maximum load on cylinder 2: 51560 lb
Maximum load on cylinder 3: 51280 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 4052.9 psi
Compressive strength of cylinder 2: 4101.8 psi
Compressive strength of cylinder 3: 4079.6 psi
Compressive strength (to nearest 10 psi): 4080 psi
General comments (publicly viewable) (Max 1000 characters): please send results to: kevin.melendez@dot.ca.gov

Test was verified on 6/16/2026