Summary for Test 2026-02-05-25-1

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 1000802
DEA: 07346804
EFIS: 0718000079
DIST-CO-RTE-PM07-VEN-232-0.4/R4.1
Award Date02/04/2025
Closeout DateNot set
Work DescriptionCOLD PLANE AND OVERLAY WITH HMA & RHMA.
Location DescriptionVENTURA COUNTY IN AND NEAR OXNARD FROM ROUTE 232/101 SEPARATION TO ROUTE 118
QA Service Level1 (Verified on 01/27/2025)

Sample Information

Sample Taken Date02/05/2026 Sample Unique Key25
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing02/06/2026
Sample typeQuality Assurance A brief description of the sampleLCB-RSC
The quantity of what the sample constitutes60 CY of 161 CY From where was the sample collectedJob Site
First name of sampler or witnessed byMike Last name of sampler or witnessed byDillon
Title of samplerField Technician Telephone number of sampler909-701-8239
Laboratory sample identification26-0490 Linked DIME Sample ID
The fabricator/manufacturer/facility nameGeorge L Throop Co. Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number2024-LCBRS
The truck number from where the sample was collected The batch plant ticket number from where the sample was collectedVolumetric Truck
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedLoad 6 Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2026-02-05-25
DIME Test ID: 2026-02-05-25-1
Testing Lab: Kleinfelder, Incorporated - Los Angeles
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2026-02-13

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Jeffrey Diaz
Date of test: 02/12/2026
Capped in accordance with?: ASTM C39 - Ground End
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.00 in
Maximum load on cylinder 1: 33511 lb
Maximum load on cylinder 2: 31979 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Age of specimen: 7 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength (to nearest 10 psi): 1160 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 2/13/2026