Summary for Test 2025-06-19-121-7
Test performed: CTM 521-June 2020Project Information
| Project Identifiers | Project ID: 1000365 DEA: 033H9014 EFIS: 0323000075 |
|---|---|
| DIST-CO-RTE-PM | 03-SOL,YOL-50,80,113-Var |
| Award Date | 09/27/2024 |
| Closeout Date | Not set |
| Work Description | HMA, RHMA, SIGN STRUCTURE, CAMERA SYSTEMS, & FO CABLE SYSTEMS. |
| Location Description | SOLANO AND YOLO COUNTIES AT VARIOUS LOCATIONS |
| QA Service Level | 1 (Verified on 09/17/2024) |
Sample Information
| Sample Taken Date | 06/19/2025 | Sample Unique Key | 121 |
|---|---|---|---|
| Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 06/20/2025 |
| Sample type | Quality Control | A brief description of the sample | 4x8 Cylinders |
| The quantity of what the sample constitutes | 7 | From where was the sample collected | Job Site |
| First name of sampler or witnessed by | Rafael | Last name of sampler or witnessed by | Duenas |
| Title of sampler | QC Field Technician | Telephone number of sampler | |
| Laboratory sample identification | 1626827 Set 1 | Linked DIME Sample ID | |
| The fabricator/manufacturer/facility name | Cemex Fairfield | Transportation Laboratory (TL) Number | |
| Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
| Structure name | Sign A6, STA 186+30 | Bid Item | Not set |
Material Information
| Material Type | Concrete | The concrete mix design number | 16286827 |
|---|---|---|---|
| The truck number from where the sample was collected | Load 1 | The batch plant ticket number from where the sample was collected | 0 |
| Concrete batch plant | Cemex | The fabricator/manufacturer designation for the sample | Set 1 |
| A detailed description of where the material sample was collected | Sign A6, STA 186+30 | Where the material sample would have been placed if not sampled | |
| From Lot No. | 1 | Bag Lot No. | 1 |
Test Details
DIME Sample ID: 2025-06-19-121
DIME Test ID: 2025-06-19-121-7
Testing Lab: G3 Quality, Incorporated - Cerritos
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2025-12-11
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Travis Van-Y
Date of test: 07/18/2025
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 120750 lb
Maximum load on cylinder 2: 118640 lb
Maximum load on cylinder 3: 122300 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength (to nearest 10 psi): 9590 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 12/11/2025 ✔