Summary for Test 2017-12-07-3-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 7428
DEA: 07215944
EFIS: 0700001834
DIST-CO-RTE-PM07-LA-5-4.0/5.9
Award Date08/23/2012
Closeout Date07/02/2021
Work DescriptionRECONSTRUCT AND WIDEN FREEWAY AND UNDERCROSSING STRUCTURES.
Location DescriptionLOS ANGELES COUNTY IN NORWALK FROM 0.4 MILE SOUTH OF SAN ANTONIO DRIVE UNDERCROSSING TO 0.7 MILE NORTH OF PIONEER BOULEVARD UNDERCROSSING
QA Service Level1 (Verified on 11/07/2012)

Sample Information

Sample Taken Date12/07/2017 Sample Unique Key3
Date that the sample was received by the laboratory/organization performing the testingNot set Sample typeQuality Assurance
A brief description of the sample6x12 concrete cylinders The quantity of what the sample constitutes45 CY in Girder G2 6
From where was the sample collectedFabricator First name of sampler or witnessed byDavid
Last name of sampler or witnessed byWeeks Title of samplerQA Inspector
Telephone number of sampler951-258-8382 Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameOLDCASTLE PRECAST PERRIS
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) FormL79
Structure unique identifierBridge No 50 3060 Girder G2 6 Structure nameSant Antonio Dr UC
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberUV-273
The truck number from where the sample was collectedNA The batch plant ticket number from where the sample was collected57089
Concrete batch plantOnsite The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedCastind Bed B1 Where the material sample would have been placed if not sampledCasting Bed B1 Girder G2 6
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2017-12-07-3
DIME Test ID: 2017-12-07-3-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2017-12-21

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Matthew Clayton
Date of test: 12/21/2017
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 5.99 in
Average diameter of cylinder 2: 6.00 in
Maximum load on cylinder 1: 238900 lb
Maximum load on cylinder 2: 234090 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Age of specimen: 14 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.18 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength of cylinder 1: 8477.6 psi
Compressive strength of cylinder 2: 8280.5 psi
Compressive strength (to nearest 10 psi): 8380 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 12/21/2017 ✔