Summary for Test 2025-08-23-7-1

Test performed: CTM 524-March 2013

Project Information

Project IdentifiersProject ID: 994966
DEA: 073255U4
EFIS: 0722000129
DIST-CO-RTE-PM07-LA-605-20.2/26
Award Date04/12/2023
Closeout DateNot set
Work DescriptionINDIVIDUAL SLAB REPLACEMENT, COLD PLANE AC
Location DescriptionLOS ANGELES COUNTY IN BALDWIN PARK AND IRWINDALE FROM ROUTE 10/605 SEPARATION TO 0.2 MILE NORTH OF ROUTE 210/605 SEPARATION
QA Service Level1 (Verified on 07/13/2023)

Sample Information

Sample Taken Date08/23/2025 Sample Unique Key7
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing08/23/2025
Sample typeAcceptance A brief description of the sample3- 6X6X21 Rapid Set Concrete Beams
The quantity of what the sample constitutes190 CY From where was the sample collectedJob Site
First name of sampler or witnessed byRosauro Last name of sampler or witnessed byNogoy
Title of samplerTEC Telephone number of sampler2137939321
Laboratory sample identification25-2807 Linked DIME Sample ID
The fabricator/manufacturer/facility nameSLC Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberCTS-65 EHI
The truck number from where the sample was collected10 The batch plant ticket number from where the sample was collected0
Concrete batch plant The fabricator/manufacturer designation for the sampleSLC
A detailed description of where the material sample was collectedChute discharge into wheel barrow Where the material sample would have been placed if not sampledNB605 near Ramona
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2025-08-23-7
DIME Test ID: 2025-08-23-7-1
Testing Lab: CT D07 - Materials Field Laboratory, Unit 1953
Test Method: CTM 524-March 2013: Method of Test for Flexural Strength Of Rapid Strength Concrete
Test Release Date: 2025-08-26

Test Results


Number of specimens: 3
Does the testing machine measure load or stress on the beam specimen?: Load
Fracture initiates in the tension surface: Within the Middle Third of the Span Length
Fracture occurred at a capped section: No
Is a beam dimensional correction factor used?: No
Input Type: Measured
Tester's full name: Rosauro Nogoy
Date of test: 08/26/2025
Identification number: 25-2807
Width of specimen: 6 inch
Width of specimen 2: 6 inch
Width of specimen 3: 6 inch
Depth of specimen: 6.125 inch
Depth of specimen 2: 6.125 inch
Depth of specimen 3: 6 inch
Span length of specimen: 18 inch
Span length of specimen 2: 18 inch
Span length of specimen 3: 18 inch
Maximum load applied: 9813 lb
Maximum load applied 2: 10598 lb
Maximum load applied 3: 9581 lb
Curing history and apparent moisture condition of the specimen: 3
If specimen was capped, ground or if leather shims were used: No
Defects in specimen, including numbers of beams discarded during test: 0
Age of specimen: 3 days
Age of specimen in hours: no data
Modulus of rupture: 820 psi
Modulus of rupture 2: 890 psi
Modulus of rupture 3: 840 psi
Modulus of rupture average: 850 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 8/26/2025