Summary for Test 2025-07-16-40-5

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 1000403
DEA: 120K91U4
EFIS: 1222000031
DIST-CO-RTE-PM12-ORA-91-R9.2/R11.4
Award Date01/03/2025
Closeout DateNot set
Work DescriptionCONST BRIDGES, RW, SW, PAVEMENT, DRAINAGE AND ELECTRICAL SYSTEMS.
Location DescriptionORANGE COUNTY IN ANAHEIM FROM 0.9 MILE WEST TO 1.3 MILES EAST OF LAKEVIEW AVENUE OVERCROSSING
QA Service Level1 (Verified on 08/19/2024)

Sample Information

Sample Taken Date07/16/2025 Sample Unique Key40
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing07/17/2025
Sample typeQuality Control A brief description of the sample4x8 cylinders
The quantity of what the sample constitutes6 From where was the sample collectedJob Site
First name of sampler or witnessed byAaron Last name of sampler or witnessed byLaughlin
Title of samplerQC Field Technician Telephone number of sampler
Laboratory sample identificationMix 1611614 Set 1 Linked DIME Sample ID
The fabricator/manufacturer/facility nameCemex Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure nameCIDH Pile #95 Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number1611614
The truck number from where the sample was collectedLoad 1 The batch plant ticket number from where the sample was collected0
Concrete batch plantCemex Orange The fabricator/manufacturer designation for the sampleSet 1
A detailed description of where the material sample was collectedCIDH Pile #95 Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2025-07-16-40
DIME Test ID: 2025-07-16-40-5
Testing Lab: G3 Quality, Incorporated - Cerritos
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2025-08-13

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Tristan Fortier
Date of test: 08/13/2025
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 80597 lb
Maximum load on cylinder 2: 81473 lb
Maximum load on cylinder 3: 80915 lb
Type of fracture pattern of cylinder 1: 5
Type of fracture pattern of cylinder 2: 2
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength (to nearest 10 psi): 6440 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 8/13/2025