Summary for Test 2025-07-11-49-1
Test performed: ASTM C39-10Project Information
| Project Identifiers | Project ID: 994422 DEA: 044A4414 EFIS: 0400020584 COOP: 04042909 |
|---|---|
| DIST-CO-RTE-PM | 04-SOL-37-10.2/11.2 |
| Award Date | Not set |
| Closeout Date | Not set |
| Work Description | Not set |
| Location Description | Not set |
| QA Service Level | 2 (Verified on 04/07/2023) |
Sample Information
| Sample Taken Date | 07/11/2025 | Sample Unique Key | 49 |
|---|---|---|---|
| Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 07/12/2025 |
| Sample type | Quality Control | A brief description of the sample | 4x8 cylinders |
| The quantity of what the sample constitutes | 3 4x8 cylinders | From where was the sample collected | Job Site |
| First name of sampler or witnessed by | Chase | Last name of sampler or witnessed by | Adams |
| Title of sampler | Telephone number of sampler | ||
| Laboratory sample identification | Linked DIME Sample ID | ||
| The fabricator/manufacturer/facility name | Central San Jose | Transportation Laboratory (TL) Number | |
| Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
| Structure name | Bid Item | Not set |
Material Information
| Material Type | Concrete | The concrete mix design number | D20115E1 |
|---|---|---|---|
| The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | 854783 | |
| Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
| A detailed description of where the material sample was collected | CHUTE wheel barrel | Where the material sample would have been placed if not sampled | |
| From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2025-07-11-49
DIME Test ID: 2025-07-11-49-1
Testing Lab: Construction Testing Services
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2025-08-12
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Michael Mahurin
Date of test: 08/08/2025
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 4500 lb
Maximum load on cylinder 2: 4440 lb
Maximum load on cylinder 3: 4420 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength (to nearest 10 psi): 4450 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 8/12/2025 ✔