Test performed: CTM 670-December 2013Project Information
| Project Identifiers | Project ID: 994864 DEA: 050N74U4 EFIS: 0522000025 |
|---|---|
| DIST-CO-RTE-PM | 05-SB-101-9.9/10.6 |
| Award Date | 07/10/2023 |
| Closeout Date | Not set |
| Work Description | SB 101 4D North San Ysidro to Olive Mill |
| Location Description | In Santa Barbara County in and near Santa Barbara from 0.1 mile south of San Ysidro Road Overcrossing to 0.1 north of Olive Mill Road Overcrossing |
| QA Service Level | 1 (Verified on 08/21/2023) |
Sample Information
| Sample Taken Date | 07/20/2025 | Sample Unique Key | 9 |
|---|---|---|---|
| Will the laboratory/organization for which you are a member perform testing on this material sample? | No | Date that the sample was received by the laboratory/organization performing the testing | 07/23/2025 |
| Sample type | Quality Assurance | A brief description of the sample | Dayton Superior coupler |
| The quantity of what the sample constitutes | 288 | From where was the sample collected | Job Site |
| First name of sampler or witnessed by | Faris | Last name of sampler or witnessed by | Malik |
| Title of sampler | Telephone number of sampler | ||
| Laboratory sample identification | Linked DIME Sample ID | ||
| The fabricator/manufacturer/facility name | CMC Rebar Dayton Superior | Transportation Laboratory (TL) Number | |
| Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
| Structure name | Bid Item | Not set |
Material Information
| Material Type | SMTL TM5 - Couplers | Production or Authorization Testing | Production Testing |
|---|---|---|---|
| Service or Ultimate | Service | Material Standard Code | ASTM A706 |
| Material Grade | 60 | Rebar Manufacturer | CMC |
| Coupler Manufacturer | Dayton Superior | Intermediate Assembler or Fabricator | |
| Rebar Size | #8 | Coupler Model | D250L Bar Lock |
| Coating Standards | Uncoated | Shape of Rebar | Straight |
| Rebar Hoop Diameter | Rebar Hoop Fabricator | ||
| Coupler Component Heat/Lot Number(s) | 4000005510 / 202937 | Rebar Heat Number(s) | 9008229 |
| Rebar Size 2 | 8 | Coupler Unique ID | SL-17-06 |
Test Details
DIME Sample ID: 2025-07-20-9
DIME Test ID: 2025-07-20-9-1
Testing Lab: CT HQ - Sacramento Structural Materials Testing Laboratory
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Test Release Date: 2025-07-31
Test Results
Number of Samples: 4
Input Type: Measured
Tester's full name: Steven Paine
Date of test: 07/31/2025
UTM: NA
Halo ID: na
Temperature: 0 f
| Num | Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Slip (inch) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 1 | 1 | 8 | 0.79 | 0.005 | 79250 | 100000 | service splice | Kleinfelder |
| 2 | 2 | 1 | 8 | 0.79 | 0000 | 82210 | 104000 | service splice | Kleinfelder |
| 3 | 3 | 1 | 8 | 0.79 | 0000 | 81110 | 103000 | service splice | Kleinfelder |
| 4 | 4 | 1 | 8 | 0.79 | 0000 | 81060 | 103000 | service splice | Kleinfelder |
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 7/31/2025 ✔