Summary for Test 2025-06-17-116-2
Test performed: CTM 521-June 2020Project Information
| Project Identifiers | Project ID: 1000580 DEA: 071XW104 EFIS: 0723000028 |
|---|---|
| DIST-CO-RTE-PM | 07--- |
| Award Date | Not set |
| Closeout Date | Not set |
| Work Description | VENTURA COUNTY IN CITY OF FILLMORE VEN-126REPLACE/CONSTRUCT THE FILLMORE MAINTENANCESTATION DAMAGED BY HIGH WINDS DIR\\'S EMERGENCY |
| Location Description | Not set |
| QA Service Level | 1 (Verified on 09/09/2024) |
Sample Information
| Sample Taken Date | 06/17/2025 | Sample Unique Key | 116 |
|---|---|---|---|
| Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 06/20/2025 |
| Sample type | Acceptance | A brief description of the sample | 4X8 PCC cylinders |
| The quantity of what the sample constitutes | 130 CY | From where was the sample collected | Job Site |
| First name of sampler or witnessed by | Majid | Last name of sampler or witnessed by | Karimi |
| Title of sampler | Assistant Structure Representative | Telephone number of sampler | |
| Laboratory sample identification | 25-360 | Linked DIME Sample ID | |
| The fabricator/manufacturer/facility name | State Ready Mix | Transportation Laboratory (TL) Number | 1282025 |
| Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
| Structure name | Bid Item | Not set |
Material Information
| Material Type | Concrete | The concrete mix design number | 15056 |
|---|---|---|---|
| The truck number from where the sample was collected | 1 TO 7 | The batch plant ticket number from where the sample was collected | 90166 |
| Concrete batch plant | State Ready Mix | The fabricator/manufacturer designation for the sample | |
| A detailed description of where the material sample was collected | truck chute | Where the material sample would have been placed if not sampled | |
| From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2025-06-17-116
DIME Test ID: 2025-06-17-116-2
Testing Lab: CT D07 - Materials Field Laboratory, Unit 1953
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2025-07-15
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Robert Achuela
Date of test: 07/15/2025
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.02 in
Average diameter of cylinder 3: 4.01 in
Maximum load on cylinder 1: 67141 lb
Maximum load on cylinder 2: 72114 lb
Maximum load on cylinder 3: 68307 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Type of fracture pattern of cylinder 3: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.69 in^2
Cross sectional area of cylinder 3: 12.63 in^2
Compressive strength of cylinder 1: 5341.4 psi
Compressive strength of cylinder 2: 5682.7 psi
Compressive strength of cylinder 3: 5408.3 psi
Compressive strength (to nearest 10 psi): 5480 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 7/15/2025 ✔