Summary for Test 2025-06-26-37-1

Test performed: ASTM C39-21

Project Information

Project IdentifiersProject ID: 1000285
DEA: 042Q4604
EFIS: 0419000015
DIST-CO-RTE-PM04-SF-101-0.8,3.4
Award Date08/28/2024
Closeout DateNot set
Work DescriptionBRIDGE RAIL REPLACEMENT.
Location DescriptionTHE CITY AND COUNTY OF SAN FRANCISCO AT THIRD STREET UNDERCROSSING AND AT TWENTY THIRD STREET OVERCROSSING.
QA Service Level1 (Verified on 07/15/2024)

Sample Information

Sample Taken Date06/26/2025 Sample Unique Key37
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing06/30/2025
Sample typeQuality Control A brief description of the sampleType II-V Cement Wing Wall
The quantity of what the sample constitutes6 Cylinders 4x8 From where was the sample collectedJob Site
First name of sampler or witnessed bySebastian Last name of sampler or witnessed byMofor
Title of samplerASR Telephone number of sampler5103858160
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameCemex Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure nameWing Wall Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number1521431
The truck number from where the sample was collected1 The batch plant ticket number from where the sample was collected41211711
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedKansas St/ 23rd St in SF Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2025-06-26-37
DIME Test ID: 2025-06-26-37-1
Testing Lab: CT HQ - Vallejo Field Laboratory
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2025-07-07

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: RD
Date of test: 07/03/2025
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Apparent mass of submerged cylinder 1: 9 lb
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Maximum load on cylinder 1: 60763 lb
Maximum load on cylinder 2: 60649 lb
Type of fracture pattern of cylinder 1: 5
Type of fracture pattern of cylinder 2: 5
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Age of specimen: 0 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Compressive strength of cylinder 1: 4830.0 psi
Compressive strength of cylinder 2: 4820.0 psi
Compressive strength (to nearest 10 psi): 4830 psi
Serial number of delivery ticket, if available: no data
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 7/7/2025